Diesel generator sets generate a large amount of heat during operation. For the units used in the engine room, the heat is even more difficult to dissipate. Once the diesel generator set operates in an environment with excessively high temperature, its load - carrying capacity will also decline. There are two cooling methods for diesel generators: air - cooling and water - cooling. When the air - cooling method is adopted, the maximum temperature of the diesel generator room should not exceed 35°C. If there is no condition to build vertical air intake and exhaust ducts in the diesel generator room or the area is insufficient, supply and exhaust fans need to be added to ensure the supply and discharge of air volume, which should be calculated according to the actual situation. When water - cooling is used in the diesel generator room, the air intake volume can be calculated at no less than 20 m³/(kW·h) of the rated power of the diesel engine. Design of the Diesel Generator Set ...
This blog mainly shares technical problems and solution of diesel generator set