Parallel Solution for Parallel Controller of Diesel Generator Set 2

This article continues to introduce four parallel solutions for parallel controllers of diesel generator sets.


power generating sets


3. Manual parallel connection with load

 

1) After manual parallel connection, conduct a load test to observe whether the active and reactive power distribution of each unit is uniform;

 

2) After manual parallel connection, conduct a soft loading test to observe whether there is significant overshoot or power oscillation during the loading process. If there is, adjust the load slope appropriately:

 

3) After manual parallel loading, conduct a soft unloading test; Observe whether the unloading of the generator set reaches the minimum load percentage set value before opening the circuit breaker;

 

4) After manual parallel connection, perform load surge and unload tests to observe whether there is power oscillation phenomenon in the unit.

 

4. Fully automatic parallel connection

 

When the controller is in automatic mode and the switch input port is remotely powered on with load (as required), it can perform fully automatic parallel, power on, and shutdown tests according to user requirements. There are three automatic parallel schemes:

 

1) Power on according to demand: The module with the highest priority is powered on first. When the load exceeds the maximum percentage set for the module, the module with the second highest priority is powered on, synchronized in parallel, and evenly loaded. When the load is less than the minimum shutdown percentage set by the module, the module with lower priority will be shut down after the shutdown delay is completed, and the circuit breaker will be opened for cooling and shutdown.

 

2) Power on all: All modules are turned on simultaneously. The module that reaches the load condition is closed first, and the other modules are synchronized and parallel one by one after reaching the load condition. Then the module detects the load, and when the load is less than the minimum shutdown percentage set by the module, the module with lower priority will be shut down after the shutdown delay is completed, and the circuit breaker will be opened to dissipate heat and shut down. When the load exceeds the maximum startup percentage set by the module, all remaining units that have not been turned on will be restarted.

 

3) Balanced engine running time: The generator set with less accumulated engine running time is started first. When the running time of the operating unit is greater than the balanced engine running time of other units, the unit with the least running time is scheduled to start (can be started according to demand or fully started), and other units are synchronized in parallel. Disconnect, unload and stop the machine by yourself. All generator sets cycle automatically on and off according to the size of the balanced engine running time.

 

The above is an introduction from Guangxi Dingbo Power Equipment Manufacturing Co., Ltd., which provides four parallel solutions for generator set parallel controllers. We hope it is helpful to everyone. The power range of diesel generator sets supplied by Dingbo Power is 20KW-2000KW. We welcome all enterprises and units to visit and negotiate with us sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...