This article continues to introduce four parallel solutions for parallel controllers of diesel generator sets.


power generating sets


3. Manual parallel connection with load

 

1) After manual parallel connection, conduct a load test to observe whether the active and reactive power distribution of each unit is uniform;

 

2) After manual parallel connection, conduct a soft loading test to observe whether there is significant overshoot or power oscillation during the loading process. If there is, adjust the load slope appropriately:

 

3) After manual parallel loading, conduct a soft unloading test; Observe whether the unloading of the generator set reaches the minimum load percentage set value before opening the circuit breaker;

 

4) After manual parallel connection, perform load surge and unload tests to observe whether there is power oscillation phenomenon in the unit.

 

4. Fully automatic parallel connection

 

When the controller is in automatic mode and the switch input port is remotely powered on with load (as required), it can perform fully automatic parallel, power on, and shutdown tests according to user requirements. There are three automatic parallel schemes:

 

1) Power on according to demand: The module with the highest priority is powered on first. When the load exceeds the maximum percentage set for the module, the module with the second highest priority is powered on, synchronized in parallel, and evenly loaded. When the load is less than the minimum shutdown percentage set by the module, the module with lower priority will be shut down after the shutdown delay is completed, and the circuit breaker will be opened for cooling and shutdown.

 

2) Power on all: All modules are turned on simultaneously. The module that reaches the load condition is closed first, and the other modules are synchronized and parallel one by one after reaching the load condition. Then the module detects the load, and when the load is less than the minimum shutdown percentage set by the module, the module with lower priority will be shut down after the shutdown delay is completed, and the circuit breaker will be opened to dissipate heat and shut down. When the load exceeds the maximum startup percentage set by the module, all remaining units that have not been turned on will be restarted.

 

3) Balanced engine running time: The generator set with less accumulated engine running time is started first. When the running time of the operating unit is greater than the balanced engine running time of other units, the unit with the least running time is scheduled to start (can be started according to demand or fully started), and other units are synchronized in parallel. Disconnect, unload and stop the machine by yourself. All generator sets cycle automatically on and off according to the size of the balanced engine running time.

 

The above is an introduction from Guangxi Dingbo Power Equipment Manufacturing Co., Ltd., which provides four parallel solutions for generator set parallel controllers. We hope it is helpful to everyone. The power range of diesel generator sets supplied by Dingbo Power is 20KW-2000KW. We welcome all enterprises and units to visit and negotiate with us sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Perkins Powerful 4000 Series Engine at Middle East Electricity

The Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Taking pride of place is the 4000 Series platform, which is designed to provide prime or standby power in critical applications. The evolution of the Perkins 4000 Series The steady evolution of the powerful 4000 Series has taken place over a number of years, thanks to significant investment from Perkins. Its development means the engine is used for prime and standby applications by original equipment manufacturers (OEMs) and end-users. The 4000 Series is tough and durable, provides consistent performance in the harshest conditions, and is proving to be a constant, reliable electric power source for prime applications all over the world. Perkins sells hundreds of 4000 Series engines every year into the prime power market. It has built more than 50,000 4000 Series engines for some of the world’s biggest businesses, and up to 30 pe...