Volvo Penta Engine Settings - Volvo Generator Manufacturer

Calibration and Settings of Volvo Power Generator Engine Engine: TAD1640GE, TAD1641GE, TAD1642GE,etc Inverted regulator mode Select if droop value is to be active. Alternative modes: “No droop value” or “Variable   droop value” Preset mode: “Fixed droop value” Regulator mode Select if droop value is active. Alternative modes: “Off” or “No” Preset mode: ”No” Primary regulator mode Selects the regulator to be used when the regulator   contact is closed. Alternative modes: ”Isochronous” or ”Droop value” Preset mode: ”Isochronous” Regulator gradient Determines the droop value to be used (gradient) Min. value: 10 Nm/revolution Preset value: 25 Nm/revolution Max. value: 128 Nm/revolution Stop function Preset mode: ”Stop” CIU stop function The CIU unit stop signal is energized during “Operations”   or “Stop”. Preset mode: ”Stop” Lamp test This parameter determines if a lamp test is to be performed   when the system is...