Grounding Maintenance Method of Diesel Generator

When the ground fault occurs to the generator in the diesel generator set configuration, it is characterized by loud noise, irregular jitter, temperature rise, unstable voltage, and similar excessive load. This fault is a ground fault caused by insulation damage between the generator winding and the iron core or the casing, also known as a winding ground fault. So, how should our users troubleshoot generator grounding faults? Here, Dingbo Power will share the following content with everyone for learning and reference in genset maintenance.


diesel generator container


Ground fault phenomenon


The diesel generator set can not operate normally due to the electrification of the generator housing, control line out of control, and winding short circuit heating.


Cause of malfunction


Due to dampness in the generator winding, the insulation resistance decreases; Long term overload operation of the generator; Harmful gas corrosion; Metal foreign objects invading the inside of the winding damage the insulation; Insulation damage and iron core collision during rewinding of stator winding; The end of the winding touches the end cover base; Insulation burns caused by friction between stator and rotor; The insulation of the outgoing line is damaged and collides with the shell; Overvoltage causes insulation breakdown.


Fault detection method


(1) Observation method. By visually inspecting the insulation at the end of the winding and inside the wire slot, observe for any signs of damage or blackening, and if so, indicate the grounding point.


(2) Multimeter inspection method. Use a multimeter to check the low resistance range. If the reading is very small, it indicates grounding.


(3) Megohmmeter method. Select different megohmmeters according to different levels to measure the insulation resistance of each group of resistors. If the reading is zero, it indicates that the winding is grounded. However, for generator insulation that is damp or broken down due to accidents, it needs to be determined based on experience. Generally speaking, if the pointer swings irregularly at "0", it can be considered to have a certain resistance value.


(4) Lamp test method. If the test light is on, it indicates that the winding is grounded. If sparks or smoke are found at a certain location, it is the point of winding grounding fault. If the light is slightly on, there is a grounding breakdown in the insulation. If the light is not on, but there is also a spark when the test rod is grounded, it indicates that the winding has not been broken down yet, but is severely damp. You can also tap hard wood on the edge of the shell's mouth, and when it reaches a certain point, wait for one to turn off and one to turn on, indicating that the current is on and off, then that point is the grounding point.


(5) Current burning method. Use a voltage regulating transformer. After connecting to the power supply, the grounding point will soon heat up, and the place where the insulation smokes is the grounding point. Special attention should be paid to small generators not exceeding twice the rated current for a period of no more than half a minute; For large motors, the rated current should be 20% -50% or gradually increased, and the power should be cut off immediately when smoke comes from the grounding point.


(6) Group elimination method. For the grounding point inside the iron core and with severe burning, the burnt copper wire is fused with the iron core. The method used is to divide the grounded phase winding into two halves, and so on, and finally find the grounding point.


As a professional diesel generator manufacturer, we always insist on using first-class talents to build a first-class enterprise, create first-class products, create first-class services, and strive to build a first-class domestic enterprise. If you would like to get more information welcome to contact us via sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...