Causes of Generator Set Fuel Injector Burning


There is no doubt that fuel injection nozzle burning will definitely influence the normal operation of generator set. If you find the related causes, you can quickly solve the problems.

1. Long time idling operation

Due to the diesel engine keeps running slowly for a long time, the temperature in the cylinder is low, the fuel combustion is not sufficient, the combustion chamber and fuel injection nozzle are easy to form carbon deposition. So it leads to the deterioration of working conditions for fuel injection nozzle. Especially in winter, it is even more serious under the condition of cold climate. Because the combustion chamber has carbon deposition, heat dissipation is slow, which may cause spray orifice obstruction of the fuel injection nozzle and the oil drip phenomenon may happen. The fuel stays in the nozzle head for a long time, the local high temperature will make the nozzle and thermal insulation jacket burned.

2. The fuel is not clean

Due to there are small particles of impurities in the fuel,  the needle valve and needle valve body of the fuel injector will wear. It is possible that the needle valve will be stuck in the needle valve body.Because of needle valve lag, the fuel can’t be periodically, quantitatively and quickly sprayed into the combustion chamber, the oil drip phenomenon will appear, which may cause the fuel atomization is not good and the combustion speed is reduced. Due to the burning time of the nozzle is extended, which will make the fuel injection nozzle and the thermal insulation jacket burned. When such fault occurs, there will be black smoke and chattering phenomenon.   

3. Fuel injection time is too late

The fuel injection advance angle is too small which may cause the fuel injection time is too late. If it can’t be adjusted for a long time, the local high temperature will make the fuel injection nozzle and thermal insulation jacket burned.

4. Improper assembly

If the nozzle insulation sheath is installed without cleaning, there will be a gap between the fuel injection nozzle and the insulation sheath. The gas enters into the gap, the heat insulation and cooling effect is reduced, which will cause the fuel injection nozzle and the insulation sheath burned. If the thermal insulation sheath is too tight, the nozzle will generate additional stress. Under the combined action of heat alternating load and high pressure of fuel injection, the nozzle will be broken and the needle valve will be stuck. In addition, if the insulation sheath can’t get installed during maintenance, the nozzle extends into the combustion chamber more than 4mm above the cylinder head bottom, the heat absorbed by the fuel injection nozzle will increase, which make the nozzle melted.

5. Improper use of generator set

If it lacks of coolant liquid while the diesel generator set is at work, the combustion chamber can’t be in good state of cooling, which will lead to the high temperature. This is also an important reason to cause the burning of fuel injection nozzle.

Prevention

As mentioned above, the fuel injection nozzle is one of the important equipment of diesel genset. For the nozzle maintenance, it is necessary to keep the fuel system clean and avoid purchasing the fuel from unreliable sources.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...