The emergency generator shall retain sufficient (not less than 600 mm) space around the generator for maintenance and cleaning. The ventilation system shall be adequate to meet the requirements of the combustion process and cooling of the air. If it is necessary to use a fan to supply the air, the fan should be operated at the same time when the generator is on. The air shall be directly inputted or discharged without any obstruction, that is, fire dampers, smoke gates, or adjustable air gates shall not be fitted. If the piping for the input and / or discharge of air is not entirely built in the room in which the generator is placed, but passes through an adjoining room or unit, the fire resistance of the pipe shall be equal to that of the fire resistance of the room in which the generator is placed or of the fire resistance of the room through which the generator is placed, Whichever is the greater. Emissions from combustion shall not cause nuisance to the public and shall...