Starlight Power Shares Diagnostic Function on Volvo Power Generation


Diagnostic Functionon Volvo Penta Engine

The purpose of the diagnostic function is to monitor and control the engine and EATS, as well as to protect components from damage. If a malfunction is detected the diagnostic function informs of the occurred fault in the form of a fault code. The fault code provides guidance when fault tracing. All fault codes and fault messages can be found in the Fault Code Register. The operator is warned that there is a malfunction via the instruments. Depending on the instrumentation in use, the fault message is shown in various ways. Fault codes can also be read out by the Volvo Penta diagnostic tool. Depending on the severity of the fault, the diagnostic function will take various actions to protect the engine (e.g. torque derate, idle speed only, engine shut down etc. )

DCU (Display Control unit)
1 When a fault is detected the following text is displayed:
!! ENGINE WARNING !! alternating with Press SEL for information.
2 Reduce engine speed to idle or shut down the engine.
3 Press the SEL button to get to the fault list.
The fault list shows:
hours of operation
fault messages
active/non-active faults
4 Look up the fault code in the Fault Code Register and take the necessary actions.
5 Press ESC to leave the fault list.

NOTICE! To get to the fault list when no fault codes are set, press the SEL button and select Diagnostics from the menu.

DU (Display Unit)
1 If the system detects a fault, a pop-up is shown on the display. Depending on the severity of the fault the following text will appear
ALARM STOP / PRESS ANY KEY or
WARNING! / PRESS ANY KEY; a buzzer will sound.
2 Reduce engine speed to idle or shut down the engine.
3 Press the SEL button to get to the fault list. The fault list shows fault messages and the number of hours of operation when the fault occurred.
4 Press ACK to acknowledge the fault code. The display background changes color (and the buzzer stops). The fault must be acknowledged before it can disappear from the fault list.
5 Look up the fault code in the Fault Code Register and take the necessary actions.
6 Press button 4 for at least three seconds to view SPN and FMI codes.
7 Press EXIT to leave the fault list.

CIU (Control Interface Unit)
When the system detects a malfunction, the diagnostics lamp flashes. If the diagnostics button is pressed and then released, a fault code is flashed out. The fault code consists of two groups of flashes, separated by a pause of two seconds. A fault code is obtained by counting the number of flashes in each group.

Example
pause = fault code 2.4
The fault code is stored and can be read off as long as the malfunction remains. Information about causes, effects and actions required is available in the Fault Code chapter.

Do as follows to read off the fault code:
1 Press the diagnostics button.
2 Release the diagnostics button and note down the fault that is flashed out.
3 Repeat items 1–2. A new fault code will be flashed out if more faults are stored. Repeat until the first fault code reappears.
NOTICE! When the first fault code reappears, all fault codes have been read off.
If the diagnostics button is pressed after the fault has been rectified and the fault codes have been erased, code 1.1 “No fault” will be displayed.

Easy Link Instruments

1 When a malfunction is detected this is reported by the diagnostic lamp which starts to flash.
2 Press the diagnostics button. The fault code is shown as text in the tachometer display.
3 Look up the fault code in the Fault Code Register and take the necessary actions.
4 When the fault has been rectified, the fault code disappears from the display and the diagnostics lamp goes out.

Erasing fault codes
The memory of the diagnostic function is reset when the power to the engine is disconnected. When the power is switched on again, the diagnostic function will check if there are any malfunctions in the system. If so a new fault codes is registered. If a malfunction has not been corrected it will be registered once again and has to be acknowledged again. The Volvo Penta diagnostic tool VODIA must be used to erase a fault code.

Maintenance
This chapter describes the most common maintenance items, see Maintenance Schedule page 44 for service intervals.
NOTICE! Service points which are not described here must be performed by an authorized Volvo Penta workshop.


CAUTION!
Read the chapter on Maintenance before starting work. It contains instructions on how to carry out maintenance and service operations in a safe and correct manner.

WARNING!

Care and maintenance work should be done with the engine stopped unless otherwise specified. Stop the engine before opening or removing the engine hatch/hood. Make it impossible to start the engine by removing the start key and cutting the system voltage with the main switches. Read about security measures for maintenance and service in the chapter Safety Information page 3 before you begin.

Orientation

TAD1340VE, TAD1341GE, TAD1341VE,
TAD1342GE, TAD1342VE, TAD1343GE,
TAD1343VE, TAD1344GE, TAD1344VE,
TAD1345GE, TAD1345VE, TAD1350GE,



TAD1350VE, TAD1351GE, TAD1352GE,
TAD1353GE, TAD1354GE, TAD1355GE
1 Expansion tank
2 Alternator
3 Oil filler cap, engine
4 Oil dipstick
5 Emergency Stop Switch
6 Control Panel
7 Air Filter
8 Fuel Filter
9 Fuel pre-filter with water separator
10 Control Unit, EMS
11 Turbo
12 Starter motor
13 Oil filter
14 Coolant Filter

Orientation
TAD1351VE, TAD1352VE, TAD1353VE
2 Emergency Stop Switch
3 Oil filler cap, engine
4 Oil dipstick
5 Fuel Filter
6 Fuel pre-filter with water separator
7 Control Unit, EMS
8 Turbo
9 Starter motor
10 Oil filter

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...