Compressed Air Filter and Hydraulic Systems of Volvo Penta Engine


Information about compressed air filter

All compressors supplied by Volvo Penta must be equipped with air filtration before the air inlet. Air filters are included in the compressor kit and can also be ordered separately. The compressor air filter must be changed at the same time as the engine air filter. The compressor inlet must be connected to the combustion air duct between the engine air filter and the turbocharger (if possible vertically from above). The connection point must always be positioned before the crank case ventilation connection to avoid the compressor drawing in oil. On the other hand, the distance to the turbocharger must be sufficient to prevent the pulsating compressor from affecting the turbocharger. The air inlet hose must have an inner diameter of at least 22 mm (0.87") and be suitable for hydraulic oil. When engine coolant is drained, the compressor cooling system must also be drained if there is a risk of freezing.

Hydraulic Systems


General

Volvo Penta supplies different types of hydraulic pumps. These pumps are only intended for power steering systems and are not designed for continuous use. However, Volvo Penta is able to supply a number of different flanges for engine-mounted hydraulic pumps for continuous operations. Refer to the Volvo Penta Sales Support Tool, Partner Network.

IMPORTANT!

Because hydraulic pumps involve large cyclical torque variations to the camshaft gear it is essential that pumps not supplied by Volvo Penta be approved by Volvo Penta before installation on the engine concerned.



Hydraulic Steering Pumps delivered by Volvo Penta
The pump gear is installed on a cylindrical shaft with a key. Before the gear is installed on the shaft it must be heated to maximum 200 °C (392 °F).

D9 and D16 engines

For TAD94X and TAD164X engines it is possible to order a hydraulic steering pump on which the fuel pump is end mounted on the power steering pump. There is a safety valve in the hydraulic pump, but the supplier nevertheless recommends that a flow and pressure valve be installed in the circuit. If there is no requirement for a hydraulic steering servo pump, a dummy is installed instead of the pump (in the same housing as the fuel pump. Refer to the Volvo Penta Sales Support Tool, Partner Network for technical details.

System Configuration

In order for the hydraulic pump to function satisfactorily it must be installed correctly. The following factors influence function:

Tank
Suction line
Inlet line
Drain line
Oil filter
Air filter
Hydraulic oil

Tank

In order for the hydraulic tank to function correctly a number of simple calculations need to be made. For satisfactory hydraulic function, consideration must be given when designing the tank to system venting, oil heat absorption and expansion. The collection of water and dirt is another important function. The illustration shows an optimal tank. Maximum hydraulic oil volume in the hydraulic tank must be 10 - 20 % lower than tank volume. Hydraulic oil volume Pump flow.

Heat absorption

Transmission losses occur in all hydraulic systems, as do hydraulic pump and engine losses. All of these are transformed into heat in the oil, which means a choice between cooling the oil or allowing it to absorb heat. If operational time exceeds one hour the oil will usually require cooling.

The required tank volume can be calculated according to the following:

NOTICE! Cooling capacity is not doubled if tank volume is doubled. Conversely, heat absorption capacity is doubled. Cooling capacity only increases by 50 %. Remember to adjust the size of lines, tank and filters to the systems maximum circulation flow.

Suction lin
Oil flow to pump suction must be free and without restrictions. This requires a suction line of sufficient diameter and the shortest possible length without flow limitations. Recommended flow speed: 0.5 - 1 m/s (1.6 - 3.3 ft./s).

Inlet line

Too narrow an inlet line causes unnecessary pressure losses that are transformed into heat. At a flow of 100 l/min a pressure drop of 10 bar (145 PSI) will create around 1.7 kW of heat. A flow speed of 4 to 7 m/s (13.1 - 23.0 ft./s) is recommended at a pressure of 100-300 bar (1,450 - 4,350 PSI).

Drain line

Pumps that are not self draining must have a drain line installed directly on the tank. The flow to the drain will increase with pump load. Overpressure will occur in the pump when the oil in the drain line accelerates and flow increases. This pressure must not exceed 2 bar (29 PSI) in normal conditions. A drain line the same size as the pump connection is recommended.

Oil and air filter
Nominal filter flow speed must correspond to the maximum flow that can occur in the system. For example, a system with a double-acting ram, such as a crane, can give double the pump flow in return. The following filtering speeds are recommended for maximum pump lifetime:

Clean environment or low pressure        25 μm
Dirty environment or high pressure         10 μm

Hydraulic oil

A suitable hydraulic oil grade must be used. At operational temperature oil viscosity must be 20 to 30 cSt.

General Recommendations

A high power take-off ratio (greater than 1:1) means that a smaller pump can be used. This is usually the best alternative both technically and economically. An exception is when a diesel engine must be run at high rpm, as a lower power take-off ratio is necessary to avoid overspeeding the pump.

Check
- Compare the power take-off max permissible load with the pump max permissible load.
Note that the formulae do not take frictional losses (mechanical efficiency) into account. However, the discrepancy is not greater than around 2 %.
- Use the engine power graphs and hydraulic pump data to make sure the engine is able to drive the pump.
The following formula can be used to calculate hydraulic pump power requirement:
Note that efficiency (η) varies depending on pump type and size and operational conditions.
Typical efficiency is 85 to 95 % It is important to note that a hydraulic pump with 90 % efficiency emits twice the heat as a pump with 95 % efficiency.

Note: We are diesel generator manufacturer/factory in China and can provide 25KVA to 3125KVA diesel power generator with various types, contact us at: sales@dieselgeneratortech.com.


Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...