Skip to main content

Engine Control System Installation - Volvo Penta Engines

Connection

• The installation must be prepared for well and carried out with the greatest care.
• Secure the connecting cable between the engine and instrument panel with clamps. Bear in mind that connector blocks must be mechanically secured so that they are not exposed to any pulling forces.
• The cables must not be run close by hot engine components or close to any other heat source.
Ensure that the cables are protected from mechanical wear, sharp edges and water splashes. If necessary, the cables can be run through conduits.
• As far as possible, avoid splices in the system wiring.
The cables and any splices must be accessible for inspection and service.
NOTICE! Connectors must be assembled “dry”, they must not be filled with petroleum jelly or similar.

Power supply

NOTICE! The engines are equipped with 2-pole electrical systems. This means that the battery negative cable must be connected to the engine block or the flywheel housing.
The battery positive cable may be run via a main switch to terminal 30 on the starter motor.
The battery negative cable must be connected to the engine block or the flywheel housing, close to the starter motor. Refer to the illustration below.

Battery specification

Max. battery 2x220 Ah (series connected), 1150 A CCA EN.
Battery charging
Standard for all engines is that batteries are supplied with power from the alternator
Battery cable cross-sectional area
The total length (L) of the positive and negative cables determines cable cross sectional area (A).


WARNING!
Due to fire risk, the cable area should never be less than 70 mm2 (0.1 inch2).

Engine control
Refer to System Information page 33 CIU
NO = normally open
NC = normally closed
Start lock (system voltage OFF / ON)
Engine system voltage start current (control unit) is 10
A. Ensure that other components in the installation are dimensioned for this current load.
Start switch
Switch type: closing (NO), spring loaded.
Stop switch
Switch type: closing (NO), spring loaded.
The stop switch is energized during operations via a parameter setting. In this case use a normally closed
(NC) switch.
RPM potentiometer
Nominal revolutions minus 120 rpm: 0.3–1.9 V (preset value 1.17 V)
Nominal revolutions plus 120 rpm: 1.9–4.7 V (preset value 4.5 V)
P0005827.jpg
P0005828.jpg



1500/1800 rpm switch
Two-position contact.
This function allows a frequency change from 50 to 60 Hz.
Idle switch
Two-position contact.
Closed contact provides idle rpm.
Droop value switch
Two-position contact.
The switch must be closed to provide rpm droop value.
Primary control switch
Two-position contact.
Contact, pre-heating
Two-position contact.

Instruments
Easy Link Instrument (option)
Refer to the System Information page 33 for the engine concerned.
For parallel connection of up to 20 extra VDO instruments.
The instruments will automatically find their own parameter group from the databus. Maximum Easy Link cable length is 3 m.

P0005054.jpg


The following instruments are available:
• Tachometer/operating hours
• Coolant temperature
• Oil pressure
• Oil temperature
• Battery voltage

Instrument, analog (option)
Refer to the System Information page 33 for the engine concerned.
Tachometer
Use Volvo Penta standard tachometer, graduations 0–2600 rpm. Setting code 14. Refer to installation instructions.

P0003961.jpg

Oil pressure gauge
Use Volvo Penta oil pressure gauge, graduations 0–10 bar (0–145 psi).

Oil temperature gauge
Use Volvo Penta oil temperature gauge, graduations 40–150 °C (104–302 °F).


Coolant temperature gauge
Use Volvo Penta oil temperature gauge, graduations 40–150 °C (105–300 °F).
Diagnostics switch Switch type: closing (NO), spring loaded. For reading fault codes, refer to the Calibration and Settings page 72 chapter.
Contact, pre-heater
Switch type: closing (NO), spring loaded. This contact
activates the pre-heating.

Synchronizing Engine Speed
Synchronization/load distribution
The system is adapted for GAC synchronization and load distribution. Use the EAM122 interface module when connecting to this system. When this system is used, voltage levels must be adjusted simultaneously with VODIA, according to the below.

P0005829.jpgP0003964.jpg


NOTICE! The EAM122 interface module is not sold by Volvo Penta. Contact a GAC (Governors of America Corporation) dealership.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...