Design Considerations for Diesel Generator Soundproof Enclosures

When designing the structure of a diesel generator soundproof enclosure, a number of important factors should be considered to ensure the comprehensiveness and practicality of its functions. For example, an acoustic enclosure should be able to house a diesel generator, including the diesel engine, alternator, batteries, circuit breaker, control system and noise reduction components and other relevant parts and accessories. This requires the designers to give due consideration to the rational layout of individual components in order to leave the necessary space for acoustic noise reduction, and to ensure the overall structure is stable and coordinated.

Generally, the silent generator enclosures are designed as a rectangle. This design has strong adaptability and mobility. With superb manufacturing technique, the enclosures are suitable for both indoor and outdoor use. In order to save space and reduce length, the ends of the enclosure are sometimes cut at an oblique angle, which can be used as air intake and exhaust outlets. However, this design is easy to inhale or stir up dust on the ground. Meanwhile, it is difficult to discharge hot air to the outside when installed in the building.

Generator soundproof enclosure outline dimension design considerations

Length: The length of a soundproof diesel generator enclosure shall not be less than the total length of the diesel engine, radiator and alternator, plus the length of the noise reduction inlet and exhaust chambers, and the thickness of the sound-absorbing components.

Width: The width of the enclosure should be greater than or equal to the sum of the thickness of the diesel engine, radiator and sound absorbing components.

Height: The height of the generator enclosure should be greater than or equal to the sum of the thickness of diesel engine, radiator, anti-vibration components, exhaust pipe components, radiator inlet space and the sound absorber components.

Since low-noise diesel generator sets are usually in an elongated shape, the length of the control box should be given priority when the conditions of usage are met. At the same time, try to arrange components like the control system, switches, batteries and wiring in other spaces. For some too slender models, appropriately widening the enclosures not only makes it easy to carry, but also makes the operation of the generator more stable, while its appearance becomes more coordinated and beautiful.

When determining the height of a generator enclosure, it is necessary to consider the adding water operation of the radiator and the space for water level inspection. If necessary, the water injection port can be located on the top outside of the enclosure. The high temperature components (up to 600°C) like superchargers and exhaust pipes of some models may be close to the edges of the enclosures, so the enclosure dimension should be designed with sufficient distance to avoid high temperature damage to the sound-absorbing materials or enclosure walls during prolonged operation of the unit. In addition, when the unit is started and stopped, some components vibrate drastically, so the enclosure wall should also be kept enough distance from these components to prevent collision and abnormal sound.

Operation door and access door designs of diesel generator soundproof enclosure

An enclosure should provide quick, easy access to your generator in an emergency. It should offer enough space for technicians to access the machinery for maintenance and repairs. The door for operation is usually set at one end (intake side) or both sides of the generator, located in a relatively low operating ambient temperature area. The door for operation is usually equipped with tempered glass observation window, which is convenient to check the parameters of the unit in real time, and has a certain sound insulation effect.

The design of access door must fully consider the convenience and feasibility of meeting different maintenance and operation needs. Routine generator maintenance and service, such as replacing three types of filters and adjusting frequency and voltage, should be easy to operate. For longer maintenance and service projects, such as replacing batteries and cleaning radiators, it should also be as convenient as possible. It should be able to carry out relevant operations by simply disassembling some components if necessary.

The dustproof and weatherproof design of silent generator enclosure

When used outdoors, the enclosure design of the unit must fully consider the needs of dust and adverse weather protection. Intake and exhaust ports generally adopt louver structure. Installing rain eaves on the upper edge of the enclosure can effectively reduce the rain falling on the surface of the enclosure. Adding rubber gaskets to the edges of each door on the enclosure can help prevent rain from seeping into its interior and reduce noise caused by vibration. Drain holes at the bottom of the box help prevent rainwater accumulation.

The production process design of the diesel generator soundproof enclosure

The design of the diesel generator soundproof enclosure should pay attention to the good manufacture craft in the processing and assembly to improve production efficiency and reduce costs. The enclosure should be robust enough to ensure safety and reliability during lifting and transportation. The materials it uses should be able to reduce the risk of deformation. The design goal of the enclosure is to reduce manufacturing and transportation costs while minimizing the size.

To learn more about the design considerations of diesel generator soundproof enclosures, contact us today.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

Factors to Consider When Choosing Diesel Generators for Data Centers

As the core facilities for data storage, processing and transmission, data centers’ stability and reliability are crucial in today's information age. Once the power supply interruption occurs, it can lead to data loss, business interruption, and even more serious consequences. Therefore, investing in one or more high-quality   diesel generators   for a data center is a key measure to ensure the continuity of power supply. Today, Dingbo Power will share several key factors that need to consider when purchasing data center diesel generator sets. Power requirements First of all, assess the power requirements of the data center based on the actual load conditions. This includes calculating the total power requirements of all critical equipment, as well as considering a possible increase in future needs. When selecting a diesel generator for the data center, make sure that the unit’s rated power can meet or exceed the peak load demand of the data center to ensure stable power suppl...