Design Considerations for Diesel Generator Soundproof Enclosures

When designing the structure of a diesel generator soundproof enclosure, a number of important factors should be considered to ensure the comprehensiveness and practicality of its functions. For example, an acoustic enclosure should be able to house a diesel generator, including the diesel engine, alternator, batteries, circuit breaker, control system and noise reduction components and other relevant parts and accessories. This requires the designers to give due consideration to the rational layout of individual components in order to leave the necessary space for acoustic noise reduction, and to ensure the overall structure is stable and coordinated.

Generally, the silent generator enclosures are designed as a rectangle. This design has strong adaptability and mobility. With superb manufacturing technique, the enclosures are suitable for both indoor and outdoor use. In order to save space and reduce length, the ends of the enclosure are sometimes cut at an oblique angle, which can be used as air intake and exhaust outlets. However, this design is easy to inhale or stir up dust on the ground. Meanwhile, it is difficult to discharge hot air to the outside when installed in the building.

Generator soundproof enclosure outline dimension design considerations

Length: The length of a soundproof diesel generator enclosure shall not be less than the total length of the diesel engine, radiator and alternator, plus the length of the noise reduction inlet and exhaust chambers, and the thickness of the sound-absorbing components.

Width: The width of the enclosure should be greater than or equal to the sum of the thickness of the diesel engine, radiator and sound absorbing components.

Height: The height of the generator enclosure should be greater than or equal to the sum of the thickness of diesel engine, radiator, anti-vibration components, exhaust pipe components, radiator inlet space and the sound absorber components.

Since low-noise diesel generator sets are usually in an elongated shape, the length of the control box should be given priority when the conditions of usage are met. At the same time, try to arrange components like the control system, switches, batteries and wiring in other spaces. For some too slender models, appropriately widening the enclosures not only makes it easy to carry, but also makes the operation of the generator more stable, while its appearance becomes more coordinated and beautiful.

When determining the height of a generator enclosure, it is necessary to consider the adding water operation of the radiator and the space for water level inspection. If necessary, the water injection port can be located on the top outside of the enclosure. The high temperature components (up to 600°C) like superchargers and exhaust pipes of some models may be close to the edges of the enclosures, so the enclosure dimension should be designed with sufficient distance to avoid high temperature damage to the sound-absorbing materials or enclosure walls during prolonged operation of the unit. In addition, when the unit is started and stopped, some components vibrate drastically, so the enclosure wall should also be kept enough distance from these components to prevent collision and abnormal sound.

Operation door and access door designs of diesel generator soundproof enclosure

An enclosure should provide quick, easy access to your generator in an emergency. It should offer enough space for technicians to access the machinery for maintenance and repairs. The door for operation is usually set at one end (intake side) or both sides of the generator, located in a relatively low operating ambient temperature area. The door for operation is usually equipped with tempered glass observation window, which is convenient to check the parameters of the unit in real time, and has a certain sound insulation effect.

The design of access door must fully consider the convenience and feasibility of meeting different maintenance and operation needs. Routine generator maintenance and service, such as replacing three types of filters and adjusting frequency and voltage, should be easy to operate. For longer maintenance and service projects, such as replacing batteries and cleaning radiators, it should also be as convenient as possible. It should be able to carry out relevant operations by simply disassembling some components if necessary.

The dustproof and weatherproof design of silent generator enclosure

When used outdoors, the enclosure design of the unit must fully consider the needs of dust and adverse weather protection. Intake and exhaust ports generally adopt louver structure. Installing rain eaves on the upper edge of the enclosure can effectively reduce the rain falling on the surface of the enclosure. Adding rubber gaskets to the edges of each door on the enclosure can help prevent rain from seeping into its interior and reduce noise caused by vibration. Drain holes at the bottom of the box help prevent rainwater accumulation.

The production process design of the diesel generator soundproof enclosure

The design of the diesel generator soundproof enclosure should pay attention to the good manufacture craft in the processing and assembly to improve production efficiency and reduce costs. The enclosure should be robust enough to ensure safety and reliability during lifting and transportation. The materials it uses should be able to reduce the risk of deformation. The design goal of the enclosure is to reduce manufacturing and transportation costs while minimizing the size.

To learn more about the design considerations of diesel generator soundproof enclosures, contact us today.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Perkins Powerful 4000 Series Engine at Middle East Electricity

The Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Taking pride of place is the 4000 Series platform, which is designed to provide prime or standby power in critical applications. The evolution of the Perkins 4000 Series The steady evolution of the powerful 4000 Series has taken place over a number of years, thanks to significant investment from Perkins. Its development means the engine is used for prime and standby applications by original equipment manufacturers (OEMs) and end-users. The 4000 Series is tough and durable, provides consistent performance in the harshest conditions, and is proving to be a constant, reliable electric power source for prime applications all over the world. Perkins sells hundreds of 4000 Series engines every year into the prime power market. It has built more than 50,000 4000 Series engines for some of the world’s biggest businesses, and up to 30 pe...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...