Selection of Diesel Generator Sets in the Data Center Industry

The energy consumption of data centers originates from IT equipment, lighting, cooling systems, and power distribution systems. Power supply reliability is critical for data centers. Diesel generator sets, as essential backup power equipment, can take over power supply during grid power failures, thereby preventing significant losses caused by server downtime or data loss. Below is an overview of diesel generator selection in the data center industry.

Generator power ratings selection

As key standards for diesel generator sets, ISO 8528-1 and GB/T 2820-1 define four types of generator power ratings:

Continuous Operating Power (COP)

Prime Rated Power (PRP)

Limited-Time Prime (LTP)

Emergency Standby Rating (ESP)

The generator power rating selected should be based on actual operating conditions. Choosing the right generator significantly impacts both the investment and power supply reliability of a data center. Different clients may select generator power ratings flexibly based on their specific requirements.

Cummins Power Generation pioneered the DCC (Data Center Continuous) power rating in the industry, tailored to the continuous power supply needs of data centers. This rating provides significant value for data center investment and operational management. The DCC power rating is recognized by Uptime Institute and can be used for Tier III and Tier IV certifications.

Key considerations for data center generator sets

The engine, which provides the necessary power for the generator set, is the most critical component in the selection process.

Primary consideration: Sufficient power output and dynamic response to load changes.

Due to the complexity of designing and manufacturing large-capacity diesel engines, engines from different manufacturers may vary significantly. Ensuring sufficient power output is a primary consideration, followed by the engine’s dynamic response to load fluctuations.

Trends: Small displacement with high power output.

Advances in technology have driven diesel engines toward smaller displacements and higher power outputs. Manufacturers are enhancing engine power density through innovations such as turbocharging and high-pressure clean combustion technologies. Traditional naturally aspirated engines, whose power output was proportional to displacement, are now obsolete. Key methods to improve power density include increasing air intake, optimizing mechanical efficiency, and improving combustion efficiency.

Four key factors when selecting a diesel generator for data center:

Adequate power output for requirements.

Superior dynamic performance—ability to handle single-step full load application.

Electronic fuel injection (EFI)—better load-handling characteristics.

Generator manufacturers with proven application experience and extensive case studies.

In addition to the considerations above, other factors such as harmonic loads, capacitive loads, rapid parallel system capability of genset, high-voltage generator neutral grounding, and ventilation systems should also be taken into account.

Fuel tanks and supply systems

Fuel tank capacity and design of generator sets comply with technical specifications and fire safety codes. Key requirements include:

Underground tanks: High-quality steel with anti-corrosion treatment, continuous magnetic float level sensors (4–20mA output to PLC).

Day tanks: Access covers, inlet/return/drain/overflow pipes, magnetic level gauges with local/remote (4–20mA) signals.

Fuel transfer pumps: Dual pumps with filters, check valves, and explosion-proof motors (3-phase, 50Hz, overload protection).

Control systems: Monitor tank levels, control valves/pumps, provide alarms, and integrate via Modbus-RS485.

Load bank testing

Load testing is vital for verifying generator performance during project acceptance. It validates full-load output, ventilation, exhaust, fuel supply, and electrical system design. Regular generator load bank testing during maintenance prevents issues like carbon buildup from light-load operation, ensuring long-term reliability of diesel generators.

This structured approach ensures diesel generator sets meet the stringent demands of modern data centers, balancing power reliability, efficiency, and operational safety.

Looking for a reliable power generator? Contact us today to order the right generator for your needs.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Perkins Powerful 4000 Series Engine at Middle East Electricity

The Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Taking pride of place is the 4000 Series platform, which is designed to provide prime or standby power in critical applications. The evolution of the Perkins 4000 Series The steady evolution of the powerful 4000 Series has taken place over a number of years, thanks to significant investment from Perkins. Its development means the engine is used for prime and standby applications by original equipment manufacturers (OEMs) and end-users. The 4000 Series is tough and durable, provides consistent performance in the harshest conditions, and is proving to be a constant, reliable electric power source for prime applications all over the world. Perkins sells hundreds of 4000 Series engines every year into the prime power market. It has built more than 50,000 4000 Series engines for some of the world’s biggest businesses, and up to 30 pe...