The Output Voltage of The Diesel Generator is Lower Than The Rated Value

With the advancement of technology, diesel generator sets have gradually become popular as emergency and backup power sources for daily life and enterprise production. Small gasoline generator sets have also begun to enter the daily lives of residents. Although the number of users is increasing, as mechanical equipment, their internal structure is still quite complex. Today, Guangxi Dingbo Power Equipment Manufacturing Co., Ltd., a diesel generator manufacturer, will introduce the reasons and treatment methods for the over - voltage or under - voltage of fully automatic diesel generators:

After the generator set is started and has reached the rated speed, and the field rheostat has been adjusted to the maximum position of "voltage rise", when the unit is running under no - load, if the voltage cannot be set to 1.05 times the rated voltage, it indicates that the output voltage of the generator is too low, which will cause difficulties in parallel operation, grid connection or power transfer.

 

Reasons for low output voltage of the generator:

(1) Inter - turn short - circuit in the rotor winding of the main generator.

(2) Inter - turn short - circuit in the rotor winding of the excitation generator.

(3) Inter - turn short - circuit in the stator winding of the excitation generator.

(4) Damage to the rotating rectifier module and varistor.

(5) Poor contact of the plug - ins of the excitation system components.

(6) The speed of the engine (usually a diesel or gasoline engine) is too low, resulting in too low induced electromotive force in the stator winding of the generator.

 

When the generator set is started and running normally at the rated speed, and the field rheostat has been adjusted to the minimum position of "voltage reduction", when the unit is running under no - load, if the voltage is still set to exceed 1.05 times the rated voltage, it indicates that the output voltage of the generator is too high. The rated voltage of a conventional generator set is 400V, and if it exceeds 420V, it means the generator voltage is high.

 

Reasons for the generator output voltage exceeding the rated value:

(1) The AVR is not working properly, and there is no shunt of the excitation current.

(2) The external voltage potentiometer (located on the power distribution cabinet) is broken.

(3) The current - limiting resistor R1 and its wiring.

(4) The magnetization switch is in the closed position, causing superposition with the self - magnetization voltage and exceeding the voltage regulation range of the AVR.

(5) The US setting of the AVR is improper and needs to be readjusted.

 

The voltage drops after the generator is loaded:

(1) The plug - ins of the excitation system are plugged in incorrectly.

(2) The AVR is not working properly.

 

Reasons for the diesel generator not generating electricity or the output voltage being lower than 100V:

(1) Damage to the stator winding of the main generator.

(2) Open - circuit in the rotor excitation winding of the main generator.

(3) Open - circuit in the stator winding of the excitation generator.

(4) Fault in the excitation system.

 

As a professional diesel generator manufacturer, we always insist on using first-class talents to build a first-class enterprise, create first-class products, create first-class services, and strive to build a first-class domestic enterprise. If you would like to get more information welcome to contact us via sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...