Fuel Supply Adjustment of Cummins Diesel Generator

If the fuel supply of each cylinder of Cummins diesel generator is uneven, it will directly affect the stability of the engine. You can remove the fuel injection pump and check and adjust it on the test bench. However, if there is no test bench for diesel generator and you need to check the uneven fuel supply, you can also roughly check the fuel supply of the suspected cylinder, and check and adjust the method: 

1. Prepare two glass measuring cylinders for use. If you cannot find the measuring cylinder at the moment, you can also use two identical small bottles instead.

2. Remove the high-pressure fuel pipe connector that connects the first cylinder with an excessive (or insufficient) fuel supply to the fuel injector.

3. Remove the high-pressure pipe joint connecting the normal fuel supply cylinder and the fuel injector. 

4. Insert the two fuel pipe ends into two measuring cylinders (or vials) respectively. 

5. Rotate the engine with the starter to pump fuel from the fuel injection pump.

6. When there is some diesel in the equivalent cylinder (or small bottle), place the measuring cylinder on a horizontal table to compare the amount of fuel and determine whether the fuel supply is too large or too small. If a small bottle is used instead, it can be weighed and compared. The relative position of the fork (or ring gear) on the fuel injection pump fuel adjustment rod (i.e. the gear rod) can be adjusted by changing it. 

During the operation of Cummins diesel generator, according to experience, the following points should be paid special attention:

1. Loosen the fixing screws of the fork (or gear ring, or flange sleeve), and the fuel supply can be changed by moving it slightly. Do not move it too much, otherwise it will be difficult to adjust accurately.

2. After each adjustment, confirm the tightening degree of the fixing screws.

3. When adjusting the fuel supply, it should be ensured that the fuel supply does not exceed the standard fuel supply, as the adjustment is carried out at low speeds, taking into account the impact of various factors such as fuel leakage. At this point, a significant degree of unevenness (30%) is allowed, but at high speeds, it is affected by factors such as throttling, resulting in a smaller degree of unevenness (3%). If the fuel quantity at low speeds is higher than the standard fuel supply quantity, there may be significant changes in the high-speed fuel quantity, even exceeding the rated fuel supply quantity.

4. If there is a significant difference between the large and small fuel supply on the same engine, do not adjust in a hurry. You can first adjust and install the outlet valves of the two pumps for inspection and comparison. Sometimes, this can also change the fuel supply. If the fuel supply is not changed after the adjustment, the two pumps need to be adjusted one by one. 

5. Use the Comparative law to adjust the fuel supply, and operate carefully.

The above is the introduction of Dingbo Power to the fuel supply adjustment method of Cummins diesel generator set. We hope it will be helpful to everyone. If you would to know more about diesel generator, please contact us by email: dingbo@dieselgeneratortech.com.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Perkins Powerful 4000 Series Engine at Middle East Electricity

The Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Taking pride of place is the 4000 Series platform, which is designed to provide prime or standby power in critical applications. The evolution of the Perkins 4000 Series The steady evolution of the powerful 4000 Series has taken place over a number of years, thanks to significant investment from Perkins. Its development means the engine is used for prime and standby applications by original equipment manufacturers (OEMs) and end-users. The 4000 Series is tough and durable, provides consistent performance in the harshest conditions, and is proving to be a constant, reliable electric power source for prime applications all over the world. Perkins sells hundreds of 4000 Series engines every year into the prime power market. It has built more than 50,000 4000 Series engines for some of the world’s biggest businesses, and up to 30 pe...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...