Structural Requirements for Diesel Generator Sets 2

The previous article has already introduced the structural requirements of the diesel engine, fuel system, and lubricating oil system for diesel generator sets. In this article, the professional diesel generator manufacturer - Dingbo Electric will continue to introduce the structural requirements of the starting system, cooling system, intake system, heating system, noise and shock absorption system.

 

diesel generator controller


1. Start the system

 

1) The generator should be able to start and deliver electricity within 30 degrees after a power outage in the city. The starting system equipped with an engine should be able to start 6 times, with each start lasting 6 seconds and an interval of 6 seconds. Each generator set should be equipped with a starting system.

 

2) An automatic diesel engine starting device should be installed, and the success rate of starting should not be less than 99%. When the engine runs without load within the predetermined time, it should automatically stop. At the same time, the startup system should meet the manual startup requirements.

 

2. Cooling system

 

1) The engine of a diesel generator must be equipped with a closed cooling system with sufficient capacity. The air temperature rise of the radiator should be 15 ℃ or lower, but should not exceed 18 ℃ when fully loaded.

 

2) The guide pipe of the diesel generator set adopts flange connection.

 

3) Anti corrosion measures should be considered.

 

3. Air intake system

 

An effective air filtration system should be provided based on the working environment conditions of diesel generators.

 

4. Exhaust system

 

1) All heated surfaces of the exhaust system of diesel generator sets must be protected by heat or other shielding measures.

 

2) Stainless steel elastic connections and matching flanges should be installed under the fire suppressor.

 

3) Elastic exhaust expansion joints should be installed at the exhaust outlet. The generator set manufacturer should indicate in the bidding documents whether the exhaust temperature and emission indicators comply with national standards.

 

4) The facilities between the muffler and the exhaust port (including the muffler) on the sled are provided by the manufacturer, and the muffler fixing bracket and the exhaust system after the muffler are provided by the owner.

 

5. Heating system

 

The cooling water and lubricating oil heating facilities required for rapid start-up of emergency diesel generator sets should be equipped, and a circulation system suitable for engine antifreeze during shutdown should be set up.

 

6. Noise and shock absorption system

 

The main requirements are as follows:

 

1) The full load noise of diesel generator set is less than 105dBA (1m) and 75dBA (7m).

 

2) The diesel generator set should be equipped with good special shock absorbers to eliminate 98% of the vibration and toughen the transmission of the generator set. When the generator set is fully loaded, the maximum seismic amplitude should not exceed 0.5mm.

 

3) Rated capacity within the scope of supply (natural ventilation)

 

Dingbo Power was founded in 1974 and is one of the earliest manufacturers of generators and diesel generator sets in China. If you want get more information, please feel free to send email to sales@dieselgeneratortech.com we will pay highly attention on your question.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Perkins Powerful 4000 Series Engine at Middle East Electricity

The Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Taking pride of place is the 4000 Series platform, which is designed to provide prime or standby power in critical applications. The evolution of the Perkins 4000 Series The steady evolution of the powerful 4000 Series has taken place over a number of years, thanks to significant investment from Perkins. Its development means the engine is used for prime and standby applications by original equipment manufacturers (OEMs) and end-users. The 4000 Series is tough and durable, provides consistent performance in the harshest conditions, and is proving to be a constant, reliable electric power source for prime applications all over the world. Perkins sells hundreds of 4000 Series engines every year into the prime power market. It has built more than 50,000 4000 Series engines for some of the world’s biggest businesses, and up to 30 pe...