Debugging of VE Distribution Pump for Diesel Generator 1

The preparation work before debugging the VE distribution pump of the diesel generator includes: installing the VE pump on the test bench and injecting diesel with a pressure of 0.035MPa into the inlet pipe joint; Install a pressure gauge with a range of O~1. OMPa between the return pipe joint and the pump body, and connect the return pipe; Connect the high-pressure oil pipe and fuel injector, with a specification of 6 for the high-pressure oil pipe × 2mm, the length of the first and third cylinders is 420mm, and the length of the second and fourth cylinders is 430mm. The injection pressure of the standard fuel injector is (17.2 ± 0.3) MPa, and the diameter of the throttle hole is 0.4mm. The test oil temperature is 38-42 ℃. Additionally, the solenoid valve is powered on with a 10-12V power supply. The debugging requirements for the VE distribution pump of the diesel generator are as follows:

emergency diesel generator


1. Inspection and debugging of pre stroke: The specified pre stroke (from bottom dead center) of the VE4/l1Fl900R294 fuel injection pump is (O ± 0.02) mm. During inspection, install a transparent drain pipe on the screw hole of the plug at the upper end of the fuel injection pump, slowly rotate the drive shaft of the fuel injection pump, so that the oil just flows into the drain pipe, but does not flow out of the drain pipe. Then, remove the oil pipe and replace it with a dial gauge to measure the position of the fuel injection pump plunger and record the reading. Rotate the drive shaft of the fuel injection pump so that the plunger is at the bottom dead center, which is the left limit position. Measure the position of the fuel injection pump plunger using a dial gauge and record the reading. The difference between the two readings is the pre stroke. If the pre travel does not meet the specified value, adjust it with the adjusting gasket of the plunger. If replacing the plunger gasket, the pre stroke should also be inspected and adjusted according to the above method.


2. Adjustment of the internal chamber pressure of the fuel injection pump: Adjust the speed of the diesel generator VE pump to 1500r/min, and when the intake pressure of the LDA device is 0.1MPa, the internal chamber pressure should be 0.6~0.66MPa. If the specified value is not met, the pressure regulating spring seat of the pressure regulating valve in the VE pump can be adjusted. At the same time, check whether the pressure inside the VE pump of the diesel generator also meets the corresponding requirements at other specified speeds.


Jiangsu Dingbo Power Generation Equipment Co., Ltd. is an early professional manufacturer of generators and diesel generator sets in China. The company has first-class national-level large-scale production and load testing equipment. Provide users with long-term diesel generator set sales, leasing, technical consultation, commissioning, maintenance, training services and generator set trusteeship business. If you would like to get more information welcome to contact us via sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...