Installation of Diesel Generator Set in Water Conservancy Project

Today we are going to introduce the installation inspection, material quality control and installation of diesel generator sets in water conservancy projects, hoping to help you.


Environmental inspection before installation of diesel generator set


Before the installation of diesel generator set, all civil works shall meet the following requirements in addition to the requirements of technical specifications.


1. The environment in the machine room is clean, well ventilated and dry;


2. There should be no articles that can produce acid, alkali and other corrosive gases in the machine room;


3. Ventilation and exhaust facilities shall be installed;


4. There shall be no other objects in front of the radiator of the unit.


Material quality control of diesel generator


1. The capacity specification of diesel generator set must meet the design requirements.


2. Check the main engine, accessories, special tools, spare parts and attached technical documents according to the packing list, check the certificate of conformity and factory test run records, and the engine and control cabinet shall have factory test records.


3. The appearance inspection of diesel generator set shows that the body is intact, the accessories are complete and the coating film is complete.


4. The specifications of various section steels used for installation shall meet the design requirements without obvious corrosion, and the bolts shall be tinned bolts.


5. Other auxiliary materials shall meet the design requirements and have product certificates.


Installation of diesel generator set in place


Diesel generator set is a high-speed rotating equipment. Before use, it must be correctly installed to ensure safe, reliable, economical and reasonable normal operation of the unit.


The in place installation of diesel generator set shall not only meet the following requirements, but also comply with relevant GB or IEC regulations.


1. The diesel generator set shall be installed in a horizontal state as far as possible, but the longitudinal inclined installation is allowed, and the gradient shall not be greater than 5 °;


2. The lower part of the common base of the diesel generator set shall be provided with damping measures. The specifications and models of the damping devices shall be the same. The fasteners used shall be galvanized standard parts.


When lifting the diesel generator set, the steel wire rope with sufficient strength shall be used at the lifting position of the unit, and it is not allowed to damage the oil pipe and meter box on the shaft. Lift the unit according to the technical installation procedures for hoisting, align it with the foundation centerline and the shock absorber, lift the unit, rely on the level gauge, and adjust it to the level with sizing block. The installation accuracy must meet the longitudinal and transverse levelness, and the deviation per meter shall not be greater than 0.1MM. There shall be no gap between the sizing block and the base to ensure that the force is uniform.


As a professional diesel generator manufacturer, we always insist on using first-class talents to build a first-class enterprise, create first-class products, create first-class services, and strive to build a first-class domestic enterprise. If you would like to get more information welcome to contact us via sales@dieselgeneratortech.com. 

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...