Skip to main content

300KW Cummins Diesel Generator

Diesel Generator Set Data

    Set Type: XG-300GF

    Prime Power: 300KW/375KVA

    Rated Current: 540 (A)

    Rated Frequency: 50(Hz)

    Start-up time: 5~6(s)

    Power Factor: 0.8(Lag)

    Rated Voltage: 400/230(V)



    Standard Features

    1. Engine: CCEC Cummins NTA855-G2A

    2. Radiator 50℃ max

    3. Fans are driven by belt, with safety guard

    4. 24V charge alternator

    5. Dry type air filter, fuel filter, oil filter

    6. Alternator: single bearing alternator

    7. IP23, insulation class H/H

    8. Main line circuit breaker

    9. Standard control panel

    10. Absorber

    11. Muffler

    12. User manual


    Diesel Engine Data
    Manufacturer: CCEC Cummins
    Model: NTA855-G2A
    Prime/Standby Power: 313KW/343KW
    Rated Speed: 1500(r/min)
    Cycle: 4 stroke
    Cylinder Arrangement: 6 in line
    Displacement: 14L
    Bore and Stroke: 140*152(mm)
    Compression Ratio: 14:1
    Governor Type: Electronic
    Start battery voltage: 24V DC

    Air Intake System
    Air Intake System: Turbo, Water/Air Cooling
    Max Intake Restriction: 6.25kPa
    Burning Capacity: 425L/s
    Air Flow: 8180L/s

    Exhaust System
    Exhaust Gas Flow: 1126L/s
    Exhaust Temperature: 563℃
    Max Back Pressure: 10kPa

    Fuel System
    Fuel System: PT type fuel pump
    100%( Prime Power) Load: 200g/kwh
    50%( Prime Power) Load: 203g/kwh

    Oil System
    Total Oil Capacity: 38.6L
    Oil Consumption: ≤0.24g/kwh
    Engine Oil Tank Capacity: 36L
    Oil Pressure at Rated RPM: 241-345kPa
    Cooling System
    Cooling Way: Water-cooled
    Total Coolant Capacity: 85L
    Thermostat: 82-93℃
    Max Water Temperature: 104℃

    Alternator Data
    Manufacturer: STARLIGHT/STAMFORD/SIEMENS/MARATHON/ENGGA /KEPU
    Excitation Mode: Brushless and self- exciting
    Number of phase and Access Act: 3-phase 4-wire
    Connecting Type: "Y" type connecting
    Alternator Capacity: 375KVA
    Alternator Efficiencies: 95%
    Overload: (PRP)110% load can run 1h
    Protection Level: IP22-IP23
    Insulation Class, Temperature Rise: H/H
    Telephone Influence Factor (TIF): <50
    THF: <2%
    Voltage Regulation, Steady State: ≤±1%
    Air Cooling Flow: 0.8m3/s
    Altitude: ≤1000m

    Genset Electrical Performance
    Voltage Regulation: ≥±5%
    Voltage Regulation, Stead State: ≤±1%
    Sudden Voltage Warp (100% Sudden Reduce): ≤+25%
    Sudden Voltage Warp (Sudden Increase): ≤-20%
    Voltage Stable Time (100% Sudden Reduce): ≤6S
    Voltage Stable Time (Sudden Increase): ≤6S
    Frequency Regulation, Stead State: ≤5%
    Frequency Waving: ≤1.5%
    Sudden Frequency Warp (100% SuddenReduce): ≤+12%
    Sudden Frequency Warp (Sudden Increase): ≤-10%
    FrequencyRecoveryTime(100%SuddenReduce): ≤5S
    FrequencyRecoveryTime(Sudden Increase): ≤5S

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...