Why My Generator Can Start But No Voltage Output?


After generator starts up, there is no voltage, the most possible reason is the generator has no magnetic field.

Why is there no magnetic filed in generator?

Fault phenomenon:

After standby generator set idle for a long period of time, when restart, there is no AC voltage output. Measure the main output winding, and the voltage between phases is "0" or lower than "5vac".

The reason:

Generator has not been used for a long time, resulting in losing remanence contained in iron core. The excitation coil can't establish the proper magnetic field. At this time, the generator set runs normally but does not generate voltage. This kind of fault often occurs in new generator set, generator set stored in humid environment or generator set not used for a long time.

How to deal with no magnetic field problem of generator?

1.Check the main output circuit of the generator to avoid the excitation cannot be established due to the short circuit at the output end.

2.if there is excitation and magnetization button, press the excitation and magnetization button.

3.If there is no excitation button, use the battery to magnetize it. The specific method is:

a.Use 12V DC battery, connect negative pole to "XX" terminal of AVR board, the positive pole is connected to the "X" terminal of AVR through a diode.

b.Restart the generator set and record the main stator output voltage, the voltage is close to the rated voltage, or the voltage between P2-P3 of AVR terminal is 170-250V.

c.Shut down the unit, then disconnect the battery power supply of "X" and "XX" terminals, and restart the generator set. At this time, the generator set should be able to operate normally. If there is still no voltage, it can be considered that there is a problem with the generator set or AVR.

Here is an other method of resolution:

First, look at the gloss level of the two slip rings. If there is no lustre, rub it with emery cloth until it becomes shiny. If still can not solve, use a very thin fuse and connect the three-phase four wires on the generator randomly. Then start the engine, the fuse will blow automatically, and the voltage will come up.

If you don't know the diode, open one of the iron rings on the back cover of the generator, and you can see two slip rings, then see the carbon sand. At this time, take a battery of any size, start the generator and hold the positive and negative terminals on the battery by hand, press and hold the two carbon sands corresponding to the slip ring. Do not remove until the generator voltage increases.

If it still doesn't work, exchange the positive and negative poles of the battery. If the voltage disappears immediately after removal, it indicates the diode is broken. Replace the diode.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...