What Causes Generator Voltage Transformer Failure?


What causes generator voltage transformer failure?

1.Winding turn to turn short circuit

Fault phenomenon: During operation, the temperature rises, there is discharge sound, the high-voltage fuse is blown, the secondary side voltmeter indication is unstable.

Reason: System over-voltage, long-term overload operation, aging insulation, poor manufacturing process.

2.Insulation damage between iron chips

Fault phenomenon: temperature rise during operation.

Reason: Poor insulation between iron chips; Poor service environment; Long term operation at high temperature promotes aging of insulation between iron chips.

3.Poor contact between grounding lug and iron core of diesel engine

Fault phenomenon: There is discharge sound between iron core and oil tank during operation.

Reason: The grounding plate is not inserted tightly, and the mounting screw is not tightened.

4.Core loosening

Fault phenomenon: There is abnormal vibration or noise during operation.

Reason: The iron core clamp is not clamped, and the iron chip is loose.

5.Winding break.

Fault phenomenon: During operation, there may be arc and discharge noise at the disconnection. The voltmeter indication of the broken phase is reduced or zero.

Reason:The winding leads are broken due to poor welding process, insufficient mechanical strength or unqualified outgoing wires.

6.Winding to ground insulation breakdown

Fault phenomenon: The fuse on the high voltage side of the diesel engine is continuously blown, which may cause discharge noise.

Reason: The winding insulation is aging or there are conductive sundries in the winding, the insulating oil is damped, over-voltage breakdown, serious oil shortage, etc.

7.Short circuit between winding

Fault phenomenon: the fuse on the high-voltage side is blown, the oil temperature is increased sharply, and even the fuel injection is smoking.

Reason: the winding insulation is aging, the insulating oil is damped, and there is serious oil shortage.

8.Discharge flashover between casings

Fault phenomenon: fuse on high voltage side is fused and bushing flashover is discharged.

Reason: mechanical damage of casing due to external force. There are foreign matters or small animals entering between casings, the casings are seriously polluted and the insulation is poor.

When using voltage transformer, what should we pay attention to?

1.We should operate with a suitable transformation ratio, rated capacity, accuracy level. And consider that the voltage drop caused by the secondary wiring will affect the measurement results, so the length can not be too long.

2.The primary winding of the voltage transformer is connected to the line, and the secondary winding is connected to the measuring instrument and relay. When wiring, pay attention to polarity group and phase, and do not connect them wrong.

3.The primary and secondary sides of the voltage transformer shall be equipped with fuses to prevent short circuit accidents. When working on the secondary circuit, pay attention not to short circuit the secondary side of the voltage transformer, otherwise it will cause overheating and burn the transformer.

4.One end of secondary side of voltage transformer shall be grounded for the same reason as current transformer.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...