What causes generator voltage transformer failure?

1.Winding turn to turn short circuit

Fault phenomenon: During operation, the temperature rises, there is discharge sound, the high-voltage fuse is blown, the secondary side voltmeter indication is unstable.

Reason: System over-voltage, long-term overload operation, aging insulation, poor manufacturing process.

2.Insulation damage between iron chips

Fault phenomenon: temperature rise during operation.

Reason: Poor insulation between iron chips; Poor service environment; Long term operation at high temperature promotes aging of insulation between iron chips.

3.Poor contact between grounding lug and iron core of diesel engine

Fault phenomenon: There is discharge sound between iron core and oil tank during operation.

Reason: The grounding plate is not inserted tightly, and the mounting screw is not tightened.

4.Core loosening

Fault phenomenon: There is abnormal vibration or noise during operation.

Reason: The iron core clamp is not clamped, and the iron chip is loose.

5.Winding break.

Fault phenomenon: During operation, there may be arc and discharge noise at the disconnection. The voltmeter indication of the broken phase is reduced or zero.

Reason:The winding leads are broken due to poor welding process, insufficient mechanical strength or unqualified outgoing wires.

6.Winding to ground insulation breakdown

Fault phenomenon: The fuse on the high voltage side of the diesel engine is continuously blown, which may cause discharge noise.

Reason: The winding insulation is aging or there are conductive sundries in the winding, the insulating oil is damped, over-voltage breakdown, serious oil shortage, etc.

7.Short circuit between winding

Fault phenomenon: the fuse on the high-voltage side is blown, the oil temperature is increased sharply, and even the fuel injection is smoking.

Reason: the winding insulation is aging, the insulating oil is damped, and there is serious oil shortage.

8.Discharge flashover between casings

Fault phenomenon: fuse on high voltage side is fused and bushing flashover is discharged.

Reason: mechanical damage of casing due to external force. There are foreign matters or small animals entering between casings, the casings are seriously polluted and the insulation is poor.

When using voltage transformer, what should we pay attention to?

1.We should operate with a suitable transformation ratio, rated capacity, accuracy level. And consider that the voltage drop caused by the secondary wiring will affect the measurement results, so the length can not be too long.

2.The primary winding of the voltage transformer is connected to the line, and the secondary winding is connected to the measuring instrument and relay. When wiring, pay attention to polarity group and phase, and do not connect them wrong.

3.The primary and secondary sides of the voltage transformer shall be equipped with fuses to prevent short circuit accidents. When working on the secondary circuit, pay attention not to short circuit the secondary side of the voltage transformer, otherwise it will cause overheating and burn the transformer.

4.One end of secondary side of voltage transformer shall be grounded for the same reason as current transformer.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...