Skip to main content

Faults and Elimination Methods for Emergency Diesel Generator


Fault
Fault characteristics and causes
Elimination method
Oil pressure alarm shutdown
Pressure sensor broken
Replace the pressure sensor
Poor quality of lubricating oil
Replace the lubricating oil
Oil filter is dirty
Replace the oil filter
Pressure valve failure
Repair or replace pressure valves
Oil pump failure
Replace the oil pump
Insufficient oil
Add oil
High water temperature alarm and stop
Insufficient cooling water
Add cooling water, the cooling water must be distilled water
Engine cannot start
Water temperature sensor is broken
Replace the water temperature sensor
Tubing has air
Check, exhaust air
Tank valve is not open
Open the oil tank valve
Oil tank without oil
Add fuel
Poor fuel quality
Replace the fuel
Starter motor failure
Replace the starting motor
Insufficient battery capacity
Charge the battery
Battery terminal oxidation, poor contact
Rust removal, fasten battery connection bolt
High pressure oil pump failure
Repair or replace the oil pump
Air filter is blocked
Replace or clean air filter
Diesel engine power
Fuel line, fuel filter into air or blocked
Remove air or replace fuel filter cartridge
Fuel injection pump does not atomize oil
Check for repair or replacement of coupling parts
The generator body is overheated, the ambient temperature is too high, the   temperature of the oil and cooling water is high, and the discharge temperature is also greatly increased.
Check the cooler and radiator to remove scale; check if the pipe diameter is toosmall. If the ambient temperature is too high, the ventilation should be improved to improve the cooling effect.
There is abnormal noise when the diesel engine is running.
The transmission gear is worn and the tooth gap is too large; the front cover   emits an abnormal sound, and when the engine suddenly drops, the impact sound can be heard.
Adjust the backlash and replace the gear according to the wear condition
Inlet   and the exhaust valve clearance is too large, and a loud rhythmic noise is heard at the cylinder head.
Recalibrate the valve clearance
There is no oil between the rocker arm adjusting screw and the spherical seat of the push rod. The "squeak" of dry friction is heard at the cylinder.
Add oil
Exhaust black smoke
Air filter blocked, intake air blocked
Check and clean the air filter
The fuel supply of each cylinder is uneven.
Adjust the fuel injection pump
Incorrect valve clearance and poor valve seal
Adjust the valve clearance, check the sealing cone, and eliminate the defects
Exhaust white smoke
The atomization of injector is poor, there is oil drop phenomenon, and the injection pressure is insufficient.
Check the nozzle couplings for grinding or replacement, and re-adjust the injection pressure to the specified range
Incomplete combustion in individual cylinders when the engine is just started
Increase the speed and load properly, and run more time.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Perkins Powerful 4000 Series Engine at Middle East Electricity

The Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Taking pride of place is the 4000 Series platform, which is designed to provide prime or standby power in critical applications. The evolution of the Perkins 4000 Series The steady evolution of the powerful 4000 Series has taken place over a number of years, thanks to significant investment from Perkins. Its development means the engine is used for prime and standby applications by original equipment manufacturers (OEMs) and end-users. The 4000 Series is tough and durable, provides consistent performance in the harshest conditions, and is proving to be a constant, reliable electric power source for prime applications all over the world. Perkins sells hundreds of 4000 Series engines every year into the prime power market. It has built more than 50,000 4000 Series engines for some of the world’s biggest businesses, and up to 30 pe...