Emergency Diesel Generator Moisture-proof Measures


We can install generator damp proof heater and control panel moisture-proof heater on emergency diesel generator to resolve moisture problem. Because generator damp proof heater and and control panel moisture-proof heater is optional part, when users purchase, should tell the supplier.

The attention on moisture-proof for diesel generator set:

1.Heating and drying shall be carried out in clean air, and the generator shall be blown clean with compressed air before drying. If the winding is seriously wet, it needs to be dried by hot air method first. After drying, dry with load to avoid insulation breakdown. When drying, we should put more thermometers in the parts of industrial diesel genset, so as to grasp the temperature of each part and reduce local overheating. Heating shall be carried out slowly to avoid insulation damage caused by sudden evaporation of moisture in the coil.

2.If the drying temperature does not reach the required temperature, it can be dried at a slightly lower temperature. But the time should be lengthened properly. Measure temperature and insulation resistance every 30min after drying. when the temperature is stable, measure every 1-2h and make records.

3.In the early drying stage of diesel generator set, due to the heating of winding and the evaporation of water, the insulation resistance will decrease. And then gradually rise, the speed of rise is more and more slow, final stable at a certain value.



When the insulation resistance is kept constant for more than 3 hours at a constant temperature, the drying can be finished. Either way, after drying, when the coil is cooled to 60, the insulation resistance of stator winding and hand winding shall be measured with 500V megger and shall not be less than 0.5MΩ.

In order to let the unit work normally, there should not have water, oil, sewage, corrosive gas etc. around the unit to avoid damaging the insulation of generator set. The temperature of cold air shall not be too low to avoid condensation on the winding and other conductive parts.

When making dampproof, pay attention not to affect the normal ventilation and cooling of the generator set. Always clean the dust and dirt in the ventilation duct and keep it unobstructed. For the generator that stops running for a short time for some reason, the collector ring does not need to be protected by holding brake, however, insulating cardboard, paraffin paper or asphalt paper shall be padded between the brush and the collecting ring to avoid spots on the surface of collecting ring caused by electric brush. In terms of the processing of the generator, if the paint is rusted due to falling off, the rust shall be removed in time and the antirust paint shall be applied.

Here are some other ways to dry diesel generator set:

1.Cold operation method.

When the AVR power line is disconnected, the generator set placed in dusty or humid environment for a long time can be idle for about 10 minutes. This may be enough to dry the winding surface and increase the insulation resistance to more than 1 MΩ to generate electricity.

2.Hot air method.

Remove all covers of the generator set in order to remove the moist air. Use a blower to blow in from the air inlet of the generator set. Please note that the heat source and winding should be kept at least 300 mm to avoid overheating and insulation damage, and control Surface temperature of winding. The winding surface temperature shall not exceed 85 and the inlet temperature shall not exceed 90 . Continue blowing every half hour and record the insulation resistance value. When the value is greater than the specified value, the drying process is completed. Remove the blower, close all covers, and try again.

3.Drying method of short circuit current.

Firstly, carry out the safe operation of the mechanical and electrical equipment of the unit to ensure the safe operation of the generating set. The output end of the generator set is short circuited through the short circuit piece, which shall be able to bear the rated current of the generator set. Disconnect AVR(Automatic voltage regulator) and switch to external 0 ~ 24V DC power supply, adjust DC power supply voltage to make each phase current of stator 50-70% of rated current. Stop every 30 minutes, disconnect the external excitation power supply, check and record the insulation resistance value. If the insulation resistance is greater than the specified value, the external DC power supply can be removed, and AVR can be reconnected and re-debugged. The generator set can operate at rated speed, but the speed shall be kept constant to avoid temperature instability.

4.Drying method with load.

If only the surface is wet, we can dry the unit with load. When drying, The generator set can operate at 50% of rated current load. Then increase the rated current by 65%, 85% and 100%. The load for each phase is 4 to 5 hours. During the drying process, the insulation resistance of each winding shall be tested regularly. After the insulation resistance meets the requirements, the drying can be stopped and the generator set is usually tested.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...