How to Extend Diesel Generator Service Life?


As we know that regular maintenance of diesel generator can not only prolong the service life of the genset, but also improve the performance of the unit.



Intake system

I. The intake system is mainly composed of an intake duct and an air filter.

II. The air filter configured in the medium-high diesel generator set is a dry paper air filter. The filter has a resistance indicator to indicate the blockage of the filter element. The resistance indicator should be checked before each start up and running of the unit. The air filter should be replaced immediately when all colour signs are visible from the window. The replaced air filter should be disposed of and cannot be reused. When replacing the air filter, special care should be taken to prevent dust from entering the intake system.

 Exhaust system

The industrial heavy-duty muffler equipped with medium-high diesel generator set is an absorption muffler. The working principle of the muffler is to absorb noise by installing a sound-absorbing bushing inside the muffler, which has a wide frequency range of noise reduction. The exhaust back pressure values of the muffler and the exhaust pipe are added together to obtain the exhaust back pressure value of the whole system.

Generator maintenance

Pre-operation check

I. Grounding: The generator is not grounded when it leaves the factory, and must be grounded properly according to the site regulations. Improper grounding and incorrect protection can result in damage to the generating set and even personal injury.

II. Reconnection: Most alternators can be rewired to adapt different output voltages. Before changing the voltage, check that other components are suitable for new voltages, such as power switches, current transformers, cables and ammeters, voltmeters, etc.

III. Insulation inspection

After installing the generator, first check the resistance of the coil. At this point, the automatic regulator should be disconnected, the rotating diode can be temporarily short-connected with wire, or disconnected first, and all control lines must be disconnected. Disconnect the wire between the midpoint and the ground and measure the impedance from the terminal to the ground with a 500V megger or similar instrument. The insulation resistance from machine to the ground should exceed 2MΩ. If the insulation resistance is less than 2MΩ, the coil must be dried.

Repair and maintenance tips


I. It is recommended that the user check and clean the main generator and all accessories regularly.

II. According to the generator data, the insulation performance of the coil is tested before the first use. If the generator is backed up, the insulation of the winding coil is detected every 3~6 months depending on the humidity of the storage place. In high humidity areas, it is recommended that the user install a heater in the generator to keep it dry when the machine is not in use, which will help reduce the generator's failure rate and ensure its normal service life.

III. The inside and outside of the alternator should be cleaned regularly, and the frequency of cleaning depends on the environment where the machine is located. When cleaning is required, follow these steps: Disconnect all power, wipe off all dust, dirt, oil, water and any liquid on the outside, and clean the ventilation net, as these things will enter the coil, causing the coil to overheat or break the insulation. Dust and dirt should be sucked up with a vacuum cleaner. Do not use blowing air or high-pressure water spray to clean.

IV. Incorrect installation, operation, maintenance or replacement of parts can result in serious injury or equipment damage. Service personnel must be qualified to work in electrical and mechanical services. Electric shock can cause serious personal injury and even death. When conducting electrical wiring, the user should avoid the wrong operation of direct connection between the ground and the neutral line of the generator.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...