Matters needing attention in Battery
I. There is a risk of fire and explosion, open fire or electric spark shall not be allowed near the battery.

II. Never confuse the positive and negative terminals of the battery, otherwise spark and explosion will occur.

III. The battery electrolyte contains highly corrosive sulfuric acid. When maintaining the battery, wear an acid-proof apron and a top cover or protective goggles. When adding electrolyte to the battery, be careful to add it slowly and prevent liquid splashing. Once the electrolyte accidentally splashed on the skin or clothing, immediately rinse with plenty of water.



Battery connection and disconnection
I. First connect the red wire (+) to the battery (+) pole. Then connect the black wire (-) to the battery (-) pole.

II. When disconnecting the battery, first remove the (-) wire (black), then remove the (+) wire (red).

Battery cleaning
Keep the battery dry and clean. Oxides and dirt on batteries and terminals can cause short circuits, voltage drops and discharges, especially in wet weather. Clean battery terminals and cables with brass brush to to remove oxides. Tighten the cable connector and apply protective grease or Vaseline to the joint.

Introduction to battery charging
I. The battery is dry when it is delivered to the user. Therefore, the electrolyte with the correct specific gravity (>1.5) that has been uniformly mixed should be added before use. Unscrew the top cover of the battery and slowly inject the electrolyte until it is between the two scale lines on the upper part of the metal sheet and as close as possible to the upper scale line. After adding it, please do not use it immediately. You should let the battery park for about 15 minutes. You can also connect the charger to charge it to the right amount.

II. When charging the battery for the first time, it should be noted that the continuous charging time should not exceed 4 hours. Because too long charging time will damage the service life of the battery.

III. When one of the following conditions occurs, the charging time is allowed to be extended appropriately:

a. Battery storage time is more than 3 months, charging time can be 8 hours.

b. The ambient temperature continues to exceed 30°C or the relative humidity continues to be higher than 80%, and the charging time can be 8 hours.

c. If the battery is stored for more than 1 year, the charging time can be 12 hours.

d. If the charger current output is insufficient, the low current charging time should be extended proportionally.

e. At the end of charging, check whether the liquid level of the electrolyte is sufficient, and add standard electrolyte with the correct specific gravity if necessary.

f. It should be noted that the size of the charging current and the length of the charging time should also take into account the old and new conditions of the battery and the amount of power already stored in the battery. When charging the battery, first open the battery filter cap or vent cap and check the electrolyte level and adjust with distilled water if necessary.

g. Normal operation and charging can cause some water to evaporate, which requires refilling the battery at any time. Firstly, the battery surface, especially the filling port, is thoroughly cleaned to prevent dirt from entering the battery compartment, then remove the hole plug, and distilled water is added until the appropriate liquid level.

h. In order to prevent long-term closure, the sewage in the battery compartment cannot be discharged in time, and the water droplets are prevented from condensing on the inner top wall of the cell.

i. It is necessary to open a special vent hole to facilitate proper air circulation. Make sure the battery is charged in a well-ventilated environment with no sparks or open flames nearby. Do not charge in an environment that cannot be protected from snow, and the charger should not be near water.

Starlight Power provides 25kva to 3125kva diesel generator set with good quality and competitive price. Contact us by email: sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...