Diesel
generator set shutdown
① Cummins Generator normal shutdown
a. Stop: The unit
controlled by the automatic module can stop normally by pressing the stop
button by hand; the manually controlled unit can only turn the key to the
“STOP” position, and can also achieve normal shutdown.
b. Before shutdown, the
load must be unloaded, and it is strictly forbidden to stop with load. In
general, after unloading the load, the diesel genset needs to run for 3 to 5
minutes without load before stopping.
c. When the load cable
is connected or removed, the battery's negative wiring must be turned off and
removed.
② Genset
emergency shutdown
a. The unit must be shut
down immediately if abnormal noise or odor is emitted during start-up or
operation.
b. When the unit oil
pressure suddenly drops to the limit or no oil pressure, the fault light is red
and must stop immediately.
The machine must stop
immediately:
a. When the unit water
temperature suddenly rises above the specified value and the fault light is
red.
b. When the unit output
voltage exceeds the maximum reading on the meter.
c. When there is a fire,
electric leakage or other natural disaster that may endanger the safety of the
crew and operators.
At this point, press the
emergency stop button or push the stop control handle of the fuel pump to the
stop position rapidly , the unit will quickly cut off the load, and immediately
turn off the throttle, while the red "emergency stop" indicator light
is on. The button needs to be re-screwed to release the emergency stop signal.
When the power generating set is in normal operation or is supplying power to
the equipment, if there is no special emergency, it is recommended that the
user do not perform emergency shutdown operation at will.
After
shutdown
a. Check for leaks in
the engine and machine room.
b. Close the fuel valve
c. If the unit is to
stop for a period of time, turn off the main switch.
d. Long-term shutdown
should drain fuel and cooling water, and periodically charge the battery
according to maintenance specifications.
e. When the ambient
temperature is lower than 5°C, the unit after shutdown must do antifreeze
measures to avoid freezing cracking of the body and water tank.