The
droop speed is the drop in speed with load and is a characteristic of the
governor or speed regulator for the prime mover. When used as a standalone
generator this will determine the drop in frequency. It is typically 2-4% at
full load.
When
used in conjunction with other generators (in parallel) then the generators sets will share the total load based on the droop characteristic. If they are
identical then they will share equally.
Two
generators using droop control to provide max power at 60Hz. One has a 63.4 Hz
reference and the other 61.8Hz reference for both to deliver full power at 60
Hz.
Thus
the aim of droop control is to adjust the governor speed references to firstly
achieve the correct system frequency and secondly share load in accordance with
the respective generators contribution in terms of its generating capacity.
This allows generators of different sizes to share the total load unlike
isochronous operation which does not.
Voltage
droop control- For a device that drives a load a series resistor is used to actually
decrease output voltage. Seems counter productive. It's to keep output voltage
at a bare minimum if output current goes up(voltage drops due to Ohm's Law) and
at just below the max voltage if load were to drop(Ohm's again) It's better
regulation for variances and uses less decoupling capacitors.
Frequency(speed)
Droop Control- basically this is load sharing, generating units running in
parallel. For multiple generators on the same electrical grid they will be
operating on the same frequency. Changes in frequencies or speed seen as power
output, will be reacted to by the generators and adjusted for, based on(I
believe) the droop control settings. I've seen other people discussing 3 or
different “set-ups” which I leave to them.
Reactive
Droop Compensation - A circuit arrangement that creates a droop in generator
output voltage that is proportional to the reactive load current. This circuit
arrangement makes paralleled generators share the reactive component of the
load current in proportion to the generator ratings. It also can essentially
eliminate the reactive component of circulating current which may flow between
paralleled generators.
The Reactive Droop Compensation arrangement is commonly
called the Generator Paralleling Module.
Comments
Post a Comment