Starlight TFW 15-2000KW series generator is the new electric generator which is designed and developed by the advanced technology. It conforms to the international IEC standards and the national GB/T 15548-95 (General specification for three-phase synchronous generator driven by reciprocating internal combustion). The product has such features of superior performance, reliable quality, novel structure, etc, and the product performance has reached the international advanced level.

Excellent Electrical Performance

Steady state voltage regulation ≤4 ± 0.1%
Transient voltage regulation rate ≤± 20% - 15%
Voltage setting range ≥10%UN
The line-voltage sinusoidal waveform distortion rate ≤5%
Ratio of voltage warp (Three phase loads are out of balanced) ≤5%

Excellent Structural Design

The integral salient-pole rotor is used; use special designs for iron-core
ventilation; the windings are solid and have good performance in thermal
radiating. The rotor has a full-damping. the generator works stable in a
parallel running together with another generator. Use cylindrical steel base.
The appearance of the product is novel and delicate. High-accuracy A.V.R
(Automatic voltage a regulation system) is equipped on the generator. While the
generator runs in a parallel mode, the AVR plays an important role. It
regulates the output voltage of the generator to a rated value. The A.V.R which
is integral sealed, also has the function of the low-frequency preventing from
damp, mildew and salt mist. These series generator can be divided into many
kinds by the difference in overall structure. By bearing, single bearing and
two bearings. By equipment, single machine (equipped with excitation box) and
(Equipped with control box). The end cover of the driving end is provided with
two structures, one is a convex end of the end cover, and the other is an end
cap and a connecting seat which are cast into an integral whole, so as to
facilitate top install the genset directly.

Working Conditions

Ambient air temperature ≤40°C
Altitude ≤1000m
Rated frequency and speed: 50Hz/1500r/min; 60Hz/1800r/min
Rated voltage: 400/230(V), 3-phase 4-wire system
The relative temperature of air ≤90%