Skip to main content

What Are the Components of Generator Cooling System


Coolant System – Each generator application can have a different cooling system configuration. Below is a general list of components:

  Coolant pump – Depending on engine size, belt or gear driven. Circulates coolant throughout cooling system.

  Radiator – Can be single or twin radiator design. Using two radiators to allow for two loop system allows for greater cooling capability.

  Fan – Can be belt or direct drive. Belt driven applications can use a fan clutch to allow for as needed fan engagement.

  Engine Oil Cooler – Coolant supplied to vessel. Vessel has a bundle of tubes that is immersed in coolant. Oil flows through tube bundle and is cooled by surrounding coolant.

  Intercooler – Coolant is supplied to a tube and fin bundle. Tube and fin bundle is located in a vessel. Air flows through vessel and is cooled by tube and fin bundle.

  Louvers – Used in canopy and mobile units to allow air to flow to the radiator from atmosphere. Control systems can allow for full open or full close. Advanced control systems can allow for louver to open as much as required for premium operation.

Cooling System Inspection – General cooling inspections should be completed during generator down time and while generator is in operation. Manufacturer’s recommendations always should be followed. Below are some minimum checks that can be used when recommendations are not available.



During Shutdown:
  Leak at water pump(s) weep hole.
  Damage, leaks and debris in radiator(s) fins.
  Coolant level and oil contamination. Oil in coolant could indicate leaking oil cooler bundle.
  Coolant specific gravity.
  Damage to fan, fan shroud or belts.
  Coolant leaks at hose connections.
  Oil for evidence of coolant contamination. Milky color could indicate leaking cylinder head gasket.
  Louvers should be closed during periods when generator is not in operation.
  Automatic transfer switch in correct position.

During Operation:
  Engine coolant temperature.
  Prior to coolant reaching operating temperature, make sure fan is not spinning on fan clutch applications.
  When coolant reaches operating temperature, make sure fan is spinning on fan clutch applications.
  Coolant leaks at radiator.
  Coolant leaks at hose connections.
  Coolant vapor in engine exhaust. Indicates coolant leaking in combustion chamber.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...