Coolant Temperature of Diesel Generator Is High?


Summer temperatures are high and temperatures are more unusual this summer. Some high temperatures reach 44.5°. The coolant of the diesel generator rises rapidly during such high temperature seasons. Diesel engines are prone to cylinder accidents at 100 ° water temperature and high temperature, so diesel generators should stop working or reduce the load when the coolant exceeds 95 °.



The water temperature of the diesel generator set is preferably around 80°, and the maximum temperature cannot exceed 95°! Remember not to let the temperature be too high or too low, it will cause damage to the generator set.

1. Improper use of coolant or insufficient water. The diesel engine used in construction machinery generally has a higher working temperature. The antifreeze can ensure its high boiling point and reduce the scale generated by the cooling system. If the cooling system is not removed, or the coolant is not replenished in time, the cooling performance will be degraded. To raise the temperature of the coolant.

2. The water radiator is blocked. For example, the heat sink of the water radiator has a large area of lodging, and there are oil and mud debris between the heat sinks, which will prevent the heat from being emitted. Especially when the surface of the water radiator is contaminated with organic oil, the thermal conductivity of the sludge mixture formed by the dust and the oil is smaller than that of the scale, which seriously hinders the heat dissipation effect. At this point, use a thin steel sheet to carefully return the heat sink to its original position, restore the flat shape of the heat sink, and then use compressed air or a water gun to clean it. If the water is heated and put into the cleaning solution, sneeze, the effect is better.

3. The water temperature gauge or warning light is incorrectly indicated. Including the water temperature sensor is damaged; the line is ironed or the indicator is out of order, resulting in false alarm. At this time, the surface thermometer can be used to measure the temperature at the water temperature sensor, and it is observed whether the water temperature gauge indicates the actual temperature.

4. The fan speed is too low and the blade is deformed or reversed. If the fan tape is too loose, it will slip, causing the fan speed to be too low and the air supply effect to be weakened. If the tape is too loose, it should be adjusted. If the rubber layer is aged, damaged or the fiber layer is broken, it should be replaced. When the fan blade is deformed, it can be compared with the new blade of the same specification to see if the angle between the blade and the relative rotation plane becomes smaller. If the angle is too small, the air supply strength will be insufficient.

5. The cooling water pump is faulty. The pump itself is damaged, the rotation speed is too low, the scale in the pump body is excessively deposited, and the narrowing of the passage will make the flow rate of the coolant smaller, the heat dissipation performance is lowered, and the temperature of the diesel engine oil is increased.

6. The thermostat is faulty. The function of the thermostat is to control the size cycle of the cooling system. When the thermostat is working at about 85 degrees, the valve starts to open, and the valve is fully opened at about 105 degrees. The method of checking the thermostat is to remove the thermostat, suspend it in a container filled with warm water, and place a thermometer in the water, then heat it from the bottom of the container to observe that the thermostat valve starts to open and If the water temperature is completely turned on, if the above requirements are not met or there is obvious damage, the thermostat should be replaced immediately.

7. The cylinder head gasket is damaged. If the cylinder head is burned by the high temperature gas, the high pressure gas will rush into the cooling system to make the coolant roll and boil. The method of judging whether the cylinder head is burnt is: turning off the diesel engine, waiting for a while, then restarting the diesel engine and increasing the speed. If at this time, the water radiator cap can be seen to have a large number of bubbles emerging, and at the same time, there is a small water droplet in the exhaust pipe discharged with the exhaust gas, it can be concluded that the cylinder head gasket is damaged.

8. Inappropriate fuel injection time. The injector is not working well. If the fuel supply advance angle is too early or delayed, the contact area of the high temperature gas with the cylinder wall increases during combustion, and the time is prolonged, and the heat transferred to the coolant increases, and the temperature of the coolant rises. At this time, there is a phenomenon that the power of the diesel engine is lowered and the fuel consumption is increased. If the fuel injection pressure of the injector drops, the fog will be poor, and the fuel will not be completely burned. The increase of the exhaust temperature will indirectly lead to an increase in the water temperature.

9. The diesel engine is overloaded. When the diesel power generator is overloaded, it will cause too much oil supply. When the generated heat exceeds the heat dissipation capacity of the diesel engine, the temperature of the coolant of the diesel engine will also rise. At this time, the diesel engine has more black smoke, increased fuel consumption, and abnormal sound.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Baudouan Weichai 1530KW Diesel Generator Set 16M33 Series Engine

Weichai is the earliest enterprise in China to develop and produce generator sets, with a production history of over 60 years. It mainly produces land - based and marine generator sets, including diesel - type and gas - type units. Weichai's M33 series engines include 6M33, 12M33, and 16M33 diesel engines. These are high - power high - speed diesel engines independently developed by Weichai based on the mature product platform of Baudouin's M26 series in France. The development of this series of models fills the gap in Weichai's high - speed diesel engines for power generation in the 500 - 1530kW power range, enabling effective competition with foreign brands. The M33 series Weichai engines inherit and carry forward the advanced product development and design concepts of the French Baudouin M26. They are benchmarked against international advanced engines, effectively avoiding various design defects. The product development emphasizes high reliability and low emissions. Th...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...