Troubleshooting for Starting Diesel Generator/Engine

1. Fault Phenomenon

The crankshaft rotation speed is normal when starting, but it takes a long time to start, or there are obvious signs that the crankshaft can't start.

2. Failure Cause

Air leakage in intake system; low fuel pressure; clogging of air filter; fault of water temperature sensor; malfunction of air Flowmeter; failure of idle speed control valve or additional air valve; failure of cold start injector; leak of injector; Incorrect ignition timing; starting switch to computer connection broken; cylinder compression pressure is too low.

3. Fault Diagnosis and Troubleshooting

A. Perform fault self-diagnosis. If there is a fault code, by the fault code to find the corresponding cause of failure.

B. Check the vacuum of the inlet during idling. If the vacuum degree is less than 667 kPa, the air leakage in the intake system should be checked at the joints, gaskets, vacuum hoses, exhaust gas recirculation system and fuel evaporation recovery system.

C. Check the air filter. If there is a filter plug, it should be cleaned or replaced.

D. If the engine can start normally when the throttle is about 1 / 4 open, and if the throttle is difficult to start when the throttle is completely closed, the idle speed control valve and the additional air valve should be checked to see if the idle speed control valve and the additional air valve are working properly. In cold car idling operation, unplug idle control valve harness or clamp the additional air valve hose with pliers during idle running. If engine speed does not decrease, idle speed control valve does not work properly. Idle speed control valve and its control circuit should be checked.

E. Check fuel pressure. Use a wire to short the two test sockets of the electric gasoline pump, then turn on the ignition switch to make the electric gasoline pump run. In this condition, the fuel pressure should be about 300 kPa. If the pressure is too low, check the oil pressure regulator for oil leakage, gasoline filter plug, gasoline pump maximum pump oil pressure is normal.

F. Check water temperature sensor or air Flowmeter. Unplug the water temperature sensor or air Flowmeter wire harness and measure the resistance between the water temperature sensor and the air Flowmeter terminal using a multimeter. If the resistance value does not meet the standard, it should be replaced.

G. If it is difficult to start in a cold car and start normally in a hot car, check that the injector works properly. Check whether there is a voltage of about 12 V at the plug of the wire harness of the cold starting injector. If there is no voltage, the control circuit is faulty, the cold start temperature-time switch and its control circuit should be checked. If there is a voltage at the wire harness plug during starting, check that the electromagnetic coil resistance of the cold start injector is normal and that the nozzle hole is blocked.

H. If it is not easy to start in the hot car, check that the fuel system pressure is normal after the ignition switch is off. The fuel pressure should be measured by the oil pressure meter. After turning off the ignition switch (extinguishing), the fuel pressure should be kept not less than 150 kPa within 5 min. If the pressure is too low, check for oil pressure regulators, electric gasoline pumps, injectors, etc.

I. Check ignition timing during idle run. If it does not meet the standard value, it should be adjusted

J. Check that the starting signal from the start switch to the computer is normal. If the starting signal of the starting switch is not received by the computer, the starting thickening control can not be carried out, which will lead to the difficulty of starting. To this end, check from the computer wire harness plug to start whether there is a starting switch signal to the computer. If there is no signal, check the starting switch and circuit.

K. Check cylinder compression pressure. If the pressure is too low, the engine should be removed and checked.



Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Choose a Household Mini Generator

With the improvement of people's living standards, there are more and more household appliances, such as rice cookers, microwaves, kettles, refrigerators, air - conditioners, washing machines, etc. It can be said that every household has them. But what if there is a power outage? These appliances won't work properly, and our lives will be greatly disrupted. How can we avoid this? We can use household mini - generators to provide convenience in power consumption. So, how to choose a good household mini - generator? Consider the noise level Since it is for household use, when choosing a household mini - generator, we need to check whether the noise will affect the neighbors. Generally, the seller will demonstrate the performance of the generator in advance. A good household generator can reduce noise by about 80%. Choose a generator with a moderate price Due to different brands, there are significant differences in power, and consequently, the price differences of househ...

How to Choose Efficient Diesel Generators for the Film and Television Industry?

In the film and television industry, the stability of the electricity supply during filming is crucial. Whether the equipment are the cameras or the lighting equipment on the filming site, or the post-production equipment, they all need stable and reliable power support. Unstable or interrupted power can result in interrupted filming, damage to equipment, and even affecting the progress and quality of the entire project. Therefore, investing in high-efficiency diesel generator sets has become an important measure for the film and television industry to ensure the reliable power supply for shooting. Determine the power requirements Before choosing a diesel generator set for the film and television industry, it’s necessary to figure out the total power needs, including the electricity demand of the shooting location, the total power of the electrical equipment and the time of using electricity. Also consider whether there are special needs for the generators such as low noise level and...