Gas system main parts technical & installation requirements 1. Pressure reducer Installation requirements ● Pressure reducer is a supplied accessory and shall be mounted in places with little vibration and near to the engine with distance not exceeding 2m. ● It shall be installed behind the filter and installation position shall be convenient for regular adjustment, inspection and maintenance of pressure reducer. ● Pipeline connecting to pressure reducer shall be reasonably arranged and free from interferences. ● Pressure reducer gas outlet and the bottom shall not be upward to prevent fuel gas greasy dirt from back flowing into pressure reducer. ● Screw off the top cap and adjust the screw to pressure reducer valve, turn clockwise to thicken and anticlockwise to thin (Note: such mode of regulation is only applicable to high speed regulation). 2. Low pressure gas filter Installation requirements: ● Gas filter installatio...
This blog mainly shares technical problems and solution of diesel generator set