Skip to main content

Fault Diagnosis and Troubleshooting Method for Generator


1. Generator overheating


(1) The generator does not operate in accordance with the specified technical conditions, such as too high stator voltage, iron loss increases; if the load current is too large, the copper loss of the stator winding increases; if the frequency is too low, the cooling fan speed becomes slow, affecting the heat dissipation of generator; the power factor is too low, so that the rotor excitation current increases, resulting in the rotor heating. Check whether the indication of monitoring instrument is normal. If it is abnormal, necessary adjustment and treatment must be carried out to operate the generator in accordance with the specified technical conditions.


2. The generator neutral line has abnormal voltage to the ground.

(1) Under normal circumstances, due to the influence of high harmonics or manufacturing process, the air gap under each magnetic pole is uneven and the magnetic potential is unequal, and the voltage is low. If the voltage is in the range of one to several volts, there will be no danger, do not have to deal with.

(2) The generator winding has short circuit or poor insulation to the ground, which leads to the deterioration of electrical equipment and generator performance, easy to heat. It should be repaired in time to avoid accidents.

(3) Neutral line has no voltage to ground at no load, and voltage occurs when there is load. It is caused by three-phase unbalance, and the three-phase load should be adjusted to make it basically balanced.

3. Generator current is too large.

(1) If the load is too large, the load should be reduced.

(2) If the transmission line has short circuit or grounding fault, the line should be overhauled and restored to normal after troubleshooting.

4. The generator terminal voltage is too high.

(1) If the grid voltage of generator parallel to the power grid is too high,  and the voltage of parallel generator should be reduced.

(2) If the fault of excitation device causes overexcitation, the excitation device should be repaired in time.

5. Insufficient power

Since the voltage source compound excitation compensation of the excitation device is insufficient, the excitation current required for the armature reaction cannot be provided, so that the generator terminal voltage is lower than the grid voltage and the rated reactive power cannot be delivered. The following measures should be taken:

(1) A three-phase voltage regulator is connected between the generator and the excitation reactor to increase the terminal voltage of the generator, so that the magnetic potential of the excitation device is gradually increased.

(2) Change the phase between the voltage magnetic-flux potential of the excitation device and the terminal voltage of the generator to increase the total magnetomotive force. Several thousand ohms and 10W resistors can be connected in parallel at  both ends of each phase winding of the reactor.

(3) The resistance of the varistor is reduced to increase the excitation current of the generator.

6. Stator winding insulation breakdown, short circuit

(1) The stator winding is damped. For generators that have been stopped for a long time or overhauled for a long time, the insulation resistance should be measured before putting into operation. Those who are not qualified are not allowed to put into operation. The damp generator should be dried.

(2) The winding itself is defective or improperly repaired, resulting in winding insulation breakdown or mechanical damage. The insulation material should be selected according to the specified insulation grade, the embedded winding and the dipping paint should be strictly carried out in accordance with the technical requirements.

(3) The winding is overheated. Insulation overheating will reduce insulation performance, and sometimes the insulation breakdown is quickly caused at a high temperature. Daily inspection should be strengthened to prevent the generator parts  from overheating and damaging the winding insulation.

(4) Insulation aging. Generally, generator runs for 15 ~ 20 years, winding insulation aging occurs, electrical performance changes, and even make insulation breakdown. If the insulation is found to be unqualified, replace the defective winding insulation in time to prolong the service life of the generator.


(5) Metal foreign matter enters the inside of the generator. After repairing the generator, do not leave the metal objects, parts or tools in the stator; tie the binding wire of the rotor and fasten the end parts so as not to be loosened by centrifugal force.

7. The stator core is loose.

The core is not fastened due to improper manufacturing and assembly. If the whole core is loose, for small generators, two iron plates smaller than the inner diameter of the stator winding end can be used to tighten the iron core by putting on double head bolts. After the original shape is restored, the original clamping bolt of the iron core is tightened. If the local iron core is relaxed, silicon steel sheet paint can be applied between the slack sheets, and then insert a hard insulating material into the slack parts.

8. Short circuit between iron chips

1) The iron core lamination is slack. When the generator is running, the iron core vibrates to damage the insulation; if the insulation of the iron chip is damaged or the core is partially overheated, it will cause insulation aging.

(2) There is a burr on the edge of the iron chip or mechanical damage during maintenance. Use a fine boring tool to remove the burrs, repair the damage, clean the surface, and then apply a layer of silicon steel paint.

(3) If there is solder or copper particles short iron core, the metal welding joint should be scraped or cut off to deal with the surface.

(4) The arc short circuit occurs in the winding, which may also cause the short circuit of the iron core. The burned part should be removed with a chisel and the surface should be treated.

9. The generator loses remanence and cannot generate electricity when starting.

(1) Remanence is often lost after shutdown, because the material used in the magnetic pole of the exciter is close to the soft steel, and the remanence is less. The magnetic field disappears when there is no current in the excitation winding after shutdown. A battery should be provided to magnetize before generating electricity.

(2) The magnetic pole of the generator loses its magnetism, and a DC current (in a short time) larger than the rated current should be applied to the winding for magnetization, that is, sufficient remanence can be restored.

10. Excitation reactor temperature of automatic excitation device is too high.

(1) The reactor coil is partially short-circuited, and the reactor should be repaired.

(2) If the air gap of the magnetic circuit of the reactor is too large, the air gap of the magnetic circuit should be adjusted.

11. When the generator starts, the voltage will not rise.

1) The excitation circuit is disconnected, preventing the voltage from rising. Check whether the excitation loop is broken and the contact is good.

(2) The residual magnet disappears. If the exciter voltmeter has no instructions to indicate that the residual magnet has disappeared, the exciter should be magnetized.

(3) The polarity of the field coil of the exciter is reversed, and its positive and negative connecting lines should be swapped.

(4) When performing some tests in the generator overhaul, the magnetic field coil is mistakenly connected to the reverse direct current, causing the residual magnet to disappear or reverse, and the magnetic field should be remagnetized. 

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f

Types of Diesel Engine and Application of Diesel Generator

This article will guide you to learn diesel engine types and important role of diesel generator. If you are interested, please keep reading.  What Are Diesel Engines? A type of internal combustion engine more accurately known as a compression ignition engine is designed to provide power by compressing the fuel at high temperature and significant pressure until it ignites. Diesel engines are either two-stroke or four-stroke .   ‘Stroke’ means the movement of the piston in the engine. Two-stroke This engine uses one stroke in each direction.   The first stroke being compression, which results in the ignition of the compressed fuel.   The return stroke brings new fuel into the cylinder. Four-stroke This engine has one compression stroke and one exhaust stroke and each one of those has a return stroke – hence, four-stroke. The compression stroke compresses the fuel/air mixture prior to ignition.   The exhaust stroke pushes the burnt gases out the exhaust. The