ELC Cooling System Maintenance - Perkins Diesel Generator


I Long-lasting coolant addition

Use premixed or concentrated coolant only for Perkins products. Perkins extenders can only be used with long-life coolants.

Mix long-life coolant with other products to reduce the life of long-life coolant. The failure to do so will reduce the life of the cooling system components unless proper remedial action is taken.


To maintain the correct balance between coolant and additives, the recommended concentration of long-life coolant (ELC) must be maintained. Lowering the proportion of the coolant also reduces the proportion of the additive. This will reduce the ability of the coolant protection system to resist pitting, cavitation, erosion and deposits.

Note: Be careful not to use conventional coolant to supplement the cooling system filled with long-life coolant (ELC). do not use the standard supplemental coolant additive (SCA). The ELC extender is only used in the RLC cooling system. Do not use standard SCA or SCA filters when using Perkins ELC.

II ELC Cooling System Cleaning

If the cooling system is already using ELC, it is not necessary to use the cleaning agent during the specified coolant replacement cycle. Cleaning agents are only required if the system has been contaminated by some other type of coolant or cooling system of diesel generator set that has been added.

When the ELC is discharged from the cooling system, it is only necessary to rinse with clean water.

After draining the cooling system and refilling the cooling system, install the filter cap. Run the engine until the coolant reaches the normal operating temperature. Shut down the engine with a normal shutdown procedure. If necessary, add a coolant mixture to fill the system to the specified level. Install the filter cap.

III Replace With Perkins ELC

To replace heavy-duty coolant with Perkins ELC, perform the following steps:

1. Drain the coolant into a suitable container
2. Dispose of the coolant according to local regulations water to remove any debris.
3. Rinse the cooling system with clean water to remove any debris.
4. Use a Perkins cleaner to clean the system. Follow the instructions on the label.
5. Drain the cleaner into a suitable container. Filling the cooling system with clean water.
6. Fill the cooling system with clean water and run the engine until it warms to 49 to 66.
7. Shut down the engine with a normal shutdown procedure. Drain the coolant into a suitable container and rinse the cooling system with clean water.
8. Repeat steps 6 and 7 until the system is completely clean.
9. Fill the cooling system with Perkins premixed ELC.
 Method to check and clean Perkins generator set after cooler core inspection and cleaning method.



Check the following conditions on the cooler: heat sink damage, corrosion, dirt, grease, inspect stains, leaves, oil and other debris, if necessary, clean the cooler.

The rear cooler core can not be removed, and the aftercooler core can be cleaned with a suitable detergent. The aftercooler must be dry before running the engine. The following are the after-cooler cleaning methods.

Compressed air is the first method to remove loose debris. Compress air is blown in the opposite direction of the fan airflow. Keep the nozzle discrete heat piece about6mm away. Slowly move the nozzle in a direction parallel to the tube. This will remove debris between the tubes.

High pressure water can also be used for cleaning. The maximum water pressure for cleaning must be less than 275kPa, and high pressure water is used to soften the sludge. Clean the rear cooler core from both sides. Be careful not to wash the core with a high concentration of corrosive detergent. High concentrations of corrosive cleaners can corrode metals inside the core and cause leakage.

Rinse the aftercooler with a suitable cleaning agent

 Clean the aftercooler with steam to remove ant residue. Rinse the fins of the aftercooler. Remove all other residual debris.

Wash the aftercooler with hot soapy water. Rinse thoroughly with clean water.

Dry the aftercooler with  compressed air. Let the air blow in the opposite direction of normal flow. Remove all liquid from the aftercooler. Make sure the aftercooler is dry.

Check the aftercooler to make sure it is clean. Pressure test the aftercooler and replace the aftercooler if necessary.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...