Use and Operation of Natural Gas Engines


3.1 Unpacking of natural gas engines

After unpacking the natural gas engine, the user shall count the engine and its accessories first in accordance with the packing list. After that, the user shall check the engine appearance for damage and the connecting pieces for looseness, and complete the following works:
Wipe the antirust coat and corrosion inhibitor on the exposed parts;

If the oil pan is not filled with oil, according to the agreement between the manufacturer and the user, fill oil into it. If the oil pan is filled with engine oil containing running-in accelerating agent before leaving our factory, we suggest that the user drain off the old oil and replace with new oil after 50 hours of trial operation.

If the engine is filled with coolant before leaving our factory based on the user needs, according to the agreement between the manufacturer and the user, the user shall check the performance of coolant after unpacking the engine. The coolant is usable if it can lower the freezing point down to -30 or -35, with a PH value between 7 and 8 (neutral) and the total hardness value is between 5 and 15°d [9 and 15°f (hardness)]; otherwise, the user shall drain off the coolant, and refill coolant containing anti-freeze additive into the engine.

3.2 Lifting of natural gas engines

Being lifted, the center line of engine crankshaft shall keep horizontal. Lifting when engine is not upright or without lifting frame is strictly prohibited. The lifting up and down shall be carried out slowly (see Figure 3-1). Figure 3-1 Lifting diagram of natural gas engines 3.3 Installation of natural gas engines

1. During installation, the center line of engine crankshaft and the input shaft axis of transmission gear (gear case, gearbox or generator, etc) shall be coaxial, and the crankshaft shall not be subject to the additional axial force caused by installation.

2. The natural gas system design shall minimize the number of connection points on the high-pressure pipeline and guarantee the convenient construction, good sealing, easy-to-check and high reliability of connection points on the pipeline.

3. The high-pressure pipeline of natural gas system shall be provided with an upstream over-current protection device to cut off the natural gas line reliably when the ignition switch is off, the engine is not running or a lot of gas is leaking from the low-pressure pipeline accidentally.

4. Test each connection point of the natural gas system with leakage detecting liquid under the rated working pressure of the natural gas system, and each connecting point shall be free from any bubble within 1 minute. Correct Wrong Operation & Maintenance Manual for WP13NG Series Gas Generators Green Power International Weichai 17 Alternatively, test each connection point of the natural gas system with a gas detector which is not lower than 25× 6 10 in measurement accuracy, and the detector shall not give an alarm.

5. The materials of gas interface parts shall fit to the gas medium, service life and ambient temperature; the interface shall be made of corrosion-resistant metallic material. The copper which is sparkproof by friction is preferred. Its copper content shall not be higher than 70% and its hardness shall not be lower than HRB60.

6. The power ground wire and the digital/analogue ground wire of the system shall be connected to the negative electrode of battery separately.

3.4 Preparatory work before startup

1. Check the coolant level If the coolant is insufficient, open the filler cap to add more coolant. If the engine is hot when the filler cap provided with a pressure relief valve and an exhaust button is opened, the operator shall stop the engine, and fill coolant after the engine is cooled down. Filling a lot of coolant when the engine is still hot is strictly prohibited, as the great change in temperature may cause parts damage.

2. Check the engine oil level The engine oil level shall be between the upper and lower scale marks of oil dipstick. Fill engine oil via the filler if necessary.

3. Check various engine accessories Check whether each engine accessory is connected reliably; if not, correct the same. Check whether the circuit of starting system is connected normally and whether the battery is charged sufficiently.

Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...