Diagnostic Function of Volvo Generator Engine


Diagnostic function of Volvo Generator Engine

The diagnostic function monitors and checks that the EDC 4 system functions normally.

Diagnostic function

The diagnostic function has the following tasks:
To detect and locate disturbances.
To report that disturbances have been detected.
To guide when troubleshooting.
Protect the engine and ensure continued operation when serious malfunctions are discovered.

Message regarding malfunction

If the diagnostic function discovers a malfunction in the EDC 4 system, this is notified via the CAN bus or the diagnostic lamp lights up or starts to flash. At the same time, the fault is stored in the control unit memory. As soon as the fault has been attended to and the ignition is turned off and on, the fault code lamp goes out. Both rectified (passive) and un-rectified (active) faults are stored in the control unit and can be read by an authorized workshop.

Fault tracing guide

If the diagnostic button is depressed (for 1-3 seconds) and then released, a fault code is flashed out from the diagnostic lamp. The fault code is found in the fault code list, with information about the reason, reaction and measures to be taken. See chapter on “Fault codes”.

Effect on the engine

The diagnostic function affects the Volvo engine in the following ways:

1. The diagnosis function has detected a minor malfunction that will not damage the engine:
Reaction: The engine is not affected. The diagnostic lamp lights up.
2. The diagnosis function has detected a serious malfunction that makes it impossible to control the engine:

Reaction: The diagnostic lamp starts to flash. Engine is shut off.

Operation

During starting

When the ignition is turned on, the diagnostics lamp and oil pressure and coolant warning lamp light for two seconds. This is to check the lamp function. If the diagnostic lamp flashes after the two seconds, this indicates a serious fault and the engine can not be started. One or more fault codes can then be flashed out. If the diagnostic lamp is lit, there are one or more less serious faults. One or more fault codes can then be flashed out.

During operation

If the diagnostic lamp starts to flash during operation:

1. Reduce engine speed to idling.
2. Press the diagnostic button (for 1-3 seconds).
3. Release the diagnostic button and make a note of the diagnostic trouble code (DTC) that is flashed out. Please refer to “Reading fault codes” below.
4. Look up the fault code in the fault code list and take the necessary measures. See chapter on “Fault codes”

If the diagnostic lamp starts to flash, the engine will be emergency stopped.
IMPORTANT! On VE engines, there is a function in the system which makes it possible to start the engine again and run it for about 25 seconds. This is so that the vehicle can be moved from a railway level crossing etc.

Reading fault codes

Fault codes can either be read via:

- The VODIA tool (including the Penta EDC4 software). Please refer to the “VODIA User’s Guide” for advice on use
- Diagnostic lamp
- CAN

Diagnostic lamp


If the diagnostic lamp is illuminated or flashes, a fault code can be read by pressing the diagnostic button (for 1-3 seconds) and then releasing it. The diagnostic lamp goes out, and a fault code is then flashed out.

The fault code consists of three groups of flashes, separated by a pause of two seconds.

The first and third group consist of short flashes (0.4 s).

The second group consists of long flashes (0.8 s). A fault code is obtained by counting the number of flashes in each group.

Example: (2 short) pause (2 long) pause

(1 short) = Fault code 2.2.1

The fault code is stored and can be read as long as the fault remains. You can find information about cause, reaction and actions in the fault code list.

Please refer to “Fault codes”.

Read as follows:

1. Press the diagnostic button (for 1-3 seconds).
2. Release the diagnostic button and make a note of the fault that is flashed out.
3. Repeat items 1-2. A new fault code is flashed out if more are stored. Repeat until the first fault code is repeated.

NOTE! When the first fault code returns, all fault codes have been read.

When all faults have been rectified:
1. Turn the ignition on and off.
2. Press the diagnostic button (for 1-3 seconds) to check whether any faults remain.
3. If there are no active faults, the diagnostic lamp will give two short flashes, in other cases the remaining non-rectified faults will be flashed out again.

CAN frames - EDC 4

The CAN - BUS has the following adjustment:
[1] The node address of EDC4 is 0.
[1] The rate of transmission is 250 kBaud.
[1] After switching power on EDC4 waits 10 sec for the other nodes before the time out diagnostic starts.
[1] During the 10 second after switching power on a receive message must be received 4 times at least, other wise there will be a time out error.
[1] When the power supply drops below 9 Volt, EDC4 will admit the other nodes a time out of 30sec.
[1] A receive message can be missing 8 times in a row before a time out Error will be generated.

1. If a message of Torque Speed Control has generated the time out, the Limp Home Function will be started. If the message will be received again it will not be accepted anymore by the EDC4 until the EDC4 is restarted again.

2. In case of other receive messages that generated a time out the last received value will be used. If a message is received again it will be accepted automatically.
[1] The node address for the received messages are 3. Only the request and engine stop request messages can be received from any node on the BUS.
The priority, resolution, repetition rate and all other information is outlined in the CAN Specification for EDC4.

Note: We are one of leading manufacturer of diesel generator in China. Can provide 25KVA to 3125KVA power generating sets with various brands, such as Cummins, Perkins, Volvo, Deutz, Ricardo, Yuchai, SDEC, Weichai and Wuxi, etc. Genset types include open type, silent type, mobile trailer type, portable type and container type generating sets.


Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

Main Structural Features of Natural Gas Engine - Weichai WP13NG Gas Generator

1.1 Main structural features of natural gas engine ● A cover per cylinder, dependable operation, easy disassembly. ● Frame-type main bearing structure and high complete machine rigidity which benefits the reliability and  service life of complete machine. ● Electronic throttle is adopted to control engine revolving speed. ● Mixture supply system uses mixer to regulate air-fuel ratio and adopts proportional mix and supercharged inter-cooling method to stabilize gas supply. ● Water-cooling middle case turbocharger applicable to gas engine features is selected and circulating  water shall be used to cool down turbocharger lubrication cooling oil so as to effectively prevent  pressure bearing lubricating oil from coking and to improve turbocharger’s reliability. ● Designed gas mixing system satisfies gas fuel features to effectively support stable lean burn and enhance thermal efficiency. ● Two pairs of friction couples of inlet, outl...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...