This article will guide you to learn conversion between diesel genset and Mains Supply through ATS. If you are interested, why not take a few minutes to read it?
What Is
ATSE?
ATSE (also known as dual power
automatic transfer switching equipment), the conversion of diesel generator
sets and mains supply can be realized by ATS. When the mains fails, ATS
automatically switches the load to the generator end of the diesel generator after
6-9 seconds delay; After the utility power is restored, the ATS automatically
switches the load to the mains terminal after a delay of 6-9 seconds. The
diesel generator set automatically stops after a cooling delay.
ATS
Components
The power automatic transfer
switch (Transfer Switch for short), it consists of one or several transfer
switching equipment and other necessary electrical appliances for detecting the
power supply circuits and automatically transferring one or more load circuits
from one power source to another.
It is a kind of dual power
automatic transfer switch with perfect performance, safety and reliability,
high degree of automation and wide range of use.
How to achieve conversion between
diesel generator set and mains supply through ATS?
First, the dual power supply
automatic conversion from the main body of the switch, which has high
resistance to shock the current ability and can be frequently converted. It has
a reliable mechanical interlock to ensure no simultaneous power transmission
failure in any state; and has zero bit power, which can be isolated from large
distance so as to withstand higher impulse voltage.
Second is the controller. The ATS
can detect the mains failure signal. When the mains fails, it can give a
control signal to the self-starting end of the generator set in time, so that
the unit can start itself and prepare for power supply. The current ATS dual
power supply controller uses microprocessor intelligent products. The detection
module should have high detection accuracy and wide parameter setting range,
including voltage, frequency, delay time, etc; with good electromagnetic
compatibility, and can withstand voltage fluctuations, surge protection,
harmonic interference, electromagnetic interference and so on.
Mandatory
requirements for dual Power supply:
1. The supply of fire control
room, fire pump, fire elevator, and smoke exhaust fan in high-pressure building
shall be equipped with automatic transfer equipment at the end of the
distribution box;
2. For the self-provided
generating equipment of a high-rise building, an automatic starting device
shall be provided and the power supply shall be provided within 30s.
3. For self-provided power
generation equipment of the second-class high-rise building, manual start-up
device should be used when there is difficulty in automatic start-up.
It can be seen from the above
mandatory regulations that the dual power supply unit should be located in the
nearest position of the load, and the dual power supply device must have
automatic conversion function. For a type of load, the standby generator set
should also have an automatic start function. Therefore, in some places, fire
protection requires an automated generating set, that is, an automatic
generator set with dual power conversion, which can also realize automatic
conversion, automatic power transmission, and high operational reliability
under unattended operation.
The switching delay of the ATS
cabinet ensures the stability of the electrical parameters of the unit power
supply or the mains power supply before switching. ATS has the function of
giving priority to the power supply. that is to say, even in the power supply
state of the generator set, at any time during this period, as long as the
mains returns to normal, it immediately switches to the mains supply.
Only a diesel generator set
equipped with a dual power automatic conversion device can achieve a seamless
transition between the diesel generator and the city power. At present, the
automatic switching screen ATS is very important emergency power supply
equipment for hospital, bank, radio station, airport, telecommunications,
hotel, etc. It can be used as an emergency power source together with the
self-starting diesel generating set. It can automatically start a diesel
generator set within 6-9 seconds of power failure and switch to the power
generation output to supply lighting, fire fighting equipment, etc.
Information
about Starlight ATSE
ATSE only be installed in the
right place, be installed, debugged and maintained by special person. All
operations (installation, connect must comply with this instruction.)
The general
Suitable for AC 660V and below,
rated frequency 50Hz, whether it is normal or not. As long as within the
technical parameters of the switch, all can be guaranteed safely and reliably
operate in the corresponding voltage grades of occasions.
Service
conditions
Ambient air temperature
The highest temperature ≤ +60℃
The lowest temperature ≥ - 20℃
The highest average temperature ≤ +60℃
The ambient air temperature is
higher than + 60℃ or below - 20℃ the user should negotiate with the
manufacturer.
Environmental temperature >60℃≤80℃ should reduce capacity selection (off about
20%);
Atmospheric
temperature
When the highest temperature + 60℃ relative humidity ≤50%. Moist or on the sea will influence
capacity when the max monthly RH is 90%.
Installation
elevation
The installation elevation ≤2000 m. When used in higher altitude, the
user should check with the manufacturer as decrease of electric strength and
cooling action.
Pollution levels
Class of pollution: class 3
Installation category
Installation category as class
IV.
Installation tilt
ATSE is a rack fixed
installation, installation tilt ≤±22.5
Use categories: AC – 33 ib
Product
features
Installation performance is good
With double row composite
contact, horizontal pull-out mechanism micromotor energy storage and
microelectric control technology, the basically zero arcing (no arc chute).
Use reliable mechanical interlock
and electric interlock, ensure higher Security
Using a zero technology, an
emergency can be forced to zero at the same time to cut off the two power
supplies.
Has obvious on/off position
indicator, padlock, and other functions. Insulate the power and the load
reliably. With high reliability and more than 1000 times using life.
Good electromagnetic
compatibility, strong anti-interference ability, no interference.
High
automaticity
Switch has multiple input/output
interface, easy to implement remote PLC control and system automation. Switch
can work without any other controller.
Beautiful shape, small volume,
light weight. The logic control board can control operation of the motor
(inside the switch) using different logic to make sure the switch on its
position.
Features
ATSE series as the main, dual
power automatic transfer switch is mainly used in the first class load and
second class load (which need back-up power) confirmed by the national
regulations, suitable for high-rise buildings, post and telecommunications,
coal and shipping, industrial assembly line, health care, military facilities,
etc. The main standby power can be grid, generator, battery, etc. The main
standby power can be customized by users. Transfer time of the main switch body
is not more than 1s. Users can make special delay when necessary. The main
power takes priority over the main standby power when supply electricity
together.