Electrical System of Volvo Penta Diesel Engine


Electrical System

The engine is equipped with a 2-pole electrical system and an alternator. System voltage is 24V.

WARNING!
Always stop the engine and break the current using the main switches before working on the engine.

Main switch

IMPORTANT!
Never disconnect the current with the main switches when the engine is running, the alternator and electronics could be damaged. The main switches must never be switched off before the engine has stopped. If the circuit between the alternator and the battery is disconnected when the engine is running, the alternator and electronics can be damaged. For the same reason the charging circuits must never be re-connected with the engine running.

Fuses

The engine is equipped with a 10 A circuit breaker which cuts the current if overloaded.
The circuit breaker is located on the left-hand side of the Volvo engine Location of Sensors.
The engine stops if the fuse trips. If the circuit breaker trips frequently, an authorized Volvo Penta workshop should be contacted to investigate the cause of the overload.

Electrical Connections

Check that electrical connections are dry, free from oxide, and that they are securely tightened.

Battery, Maintenance

WARNING!
Risk of fire and explosion. Never allow an open flame or electric sparks near the battery or batteries.

WARNING!
Never confuse the positive and negative poles on the batteries. Risk of arcing and explosion.

WARNING!
The battery electrolyte contains extremely corrosive sulfuric acid. Protect your skin and clothes when charging or handling batteries. Always use protective goggles and gloves. If battery electrolyte comes into contact with unprotected skin wash off immediately using plenty of water and soap. If battery acid comes in contact with the eyes, flush immediately with plenty of water and obtain medical assistance without delay.

Connecting and disconnecting the battery.

Connecting

1 Connect the + cable (red) to the + pole on the battery.
2 Connect the – cable (black) to the – pole on the battery.

Disconnecting
1 Remove the – cable (black).
2 Remove the + cable (red).

Cleaning

Keep the batteries clean and dry. Contamination and oxide on the batteries and battery poles can cause stray currents, voltage drop and discharge, especially in wet weather. Remove oxidation from the battery poles and terminals, using a brass brush. Tighten the terminals securely and grease them with terminal grease or petroleum jelly.

Filling

The electrolyte level should be 5–10 mm (0.2– 0.4”) above the cell plates in the battery. Top up with distilled water as required. After filling, the battery should be charged for at least 30 minutes by running the engine at idle. Some maintenance-free batteries have special instructions, which must be followed.

Battery, Charging
WARNING!
Risk of fire and explosion. Never allow an open flame or electric sparks near the battery or batteries.

WARNING!
The battery electrolyte contains extremely corrosive sulfuric acid. Protect your skin and clothes when charging or handling batteries. Always use protective goggles and gloves. If battery electrolyte comes into contact with unprotected skin wash off immediately using plenty of water and soap. If battery acid comes in contact with the eyes, flush immediately with plenty of water and obtain medical assistance without delay.

WARNING!
Never confuse the positive and negative poles on the batteries. Risk of arcing and explosion.

IMPORTANT!
Observe the instruction manual for the battery charger carefully. To avoid the risk of electrochemical corrosion when an external charger is connected, the battery cables should be removed from the batteries before the charger is connected. Always switch off the charging current before the charging clips are removed.
Charge batteries if they have become discharged. During charging, unscrew the cell plugs but leave them in the plug holes. Ventilate well, especially if the batteries are charged in an enclosed space.
If the engine is not used for a longer period of time, the batteries should be fully charged, then possibly trickle charged. Refer to the battery manufacturer’s recommendations). Batteries are damaged by being left discharged, and can also freeze and burst more easily in cold weather.
Special instructions apply to boost charging. Boost charging can shorten battery life, and should therefore be avoided.

Storage
To prevent the engine and other equipment from being harmed during long (2 months or more) periods out of service, it must be conserved. Because it is of utmost importance that the conservation be performed correctly, we have compiled a checklist covering the most important points. Before taking the engine out of service for long periods, it should be checked by a Volvo Penta dealer for possible need of overhaul or repair.

CAUTION!
Read the chapter on Maintenance before starting work. It contains instructions on how to carry out maintenance and service operations in a safe and correct manner.

WARNING!
Conservations oils can be flammable and dangerous to inhale. Ensure good ventilation. Use a protective face mask when spraying.

IMPORTANT!
Remember the following must be considered when cleaning with a high-pressure water jet: Never point highpressure water jets directly at seals, rubber hoses or electrical components. Never use the high-pressure function when washing the engine.

For up to 8 month’s stoppage:
Change the oil and oil filter on the engine, then run the engine until warm.

More than 8 month's stoppage:
Conserve the lubrication and fuel systems with conservation oil. Refer to the section Conservation of the lubrication and fuel systems for more than 8 months’ stoppage.
Make sure the coolant has adequate antifreeze properties. Top up as necessary.
Alternatively, you can drain the coolant (also drain the coolant filter).
Drain any water and contamination from the fuel filters and fuel tank. Fill the fuel tank completely, to avoid condensation.
Disconnect the battery cables, clean and charge the batteries. Trickle charge the batteries while the equipment is in storage. A poorly charged battery can freeze and burst.
Clean the outside of the engine. Do not use a high pressure washer for engine cleaning. Touch up paint damage with Volvo Penta original paint.
Check and rust-proof any control cables.
Put a note on the engine with the date, type of conservation and the conservation oil used.
Cover the air filter, exhaust pipe and engine if necessary.

Bringing out of storage
Remove any covers from the engine, air filter and exhaust pipe.
Fill the engine with the correct grade of oil into the engine, as necessary, refer to Technical Data, Lubrication System. Install a new oil filter if the filter was not changed during conservation.
Install new fuel filters and bleed the fuel system.
Check the drive belt(s).
Check the condition of all rubber hoses, and retighten the hose clamps.
Close the drain taps and install any drain plugs.
Check the coolant level. Top up as necessary.
Connect the fully charged batteries.
Start the engine and warm it up at fast idle with no load.
Check that no oil, fuel or coolant leakage occurs.
Conservation of the lubrication and fuel systems for more than 8 months’ stoppage:
Drain the engine oil and fill up with conservation oil* to just over the MIN marking on the dipstick.
Connect the fuel suction and return hoses to a 1/3 full jerrican containing conservation oil* and 2/3 diesel fuel.
Bleed the fuel system.
Start the engine and run at a fast idle until about 2 liters (0.6 US gal) of the fluid in the jerrican have been used. Stop the engine and re-connect the fuel suction and return lines.
Drain the conservation oil from the engine.
Follow the other instructions on the previous page.
* Conservation oils are sold by oil companies.


Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...