Skip to main content

Connection and Parameter Setting of Volvo Industrial Engine


Connection of Volvo Industrial Engine

Control unit
The control unit must be installed separately from the engine. Control unit working temperature must be between - 40 °C to +85 °C.
Accelerator pedal (VE engines)
Idling: 0-5 V (standard value 0.3 V)
Full throttle: 0-5 V (default value 4.6 V)
A fault code is generated when the voltage is:
U > 4.9 V (standard value)
U < 0.1 V (standard value)
Engine speed potentiometer/external voltage input (GE engines)
Rotary potentiometer for fine adjustment of engine speed (GE engines)
On 1500 rpm or 1800 rpm GE engines, the Volvo engine speed can be finely adjusted ±5 %. A fault code is generated when the voltage is:
U > 4.8 V (standard value)
U < 0.2 V (standard value)
This accelerator pedal/potentiometer corresponds to the control unit standard value (0.5 V or 4.5 V respectively).
The end position resistor is used to detect electrical faults in the accelerator/potentiometer (end position resistors are built into many accelerators/potentiometers and do not need to be added in these cases).
1500/1800 rpm switch
This function makes it possible to switch engine speed between 1500 and 1800 rpm. Switch type, two-position (NO).
Droop switch
The switch must be closed to obtain droop. Switch type, two-position (NO).
Alarm, low oil pressure
Max. power 3 W
Voltage 12 V/24 V
Alarm, high coolant temperature
Max. power 3 W
Voltage 12 V/24 V

Tachometer
Tachometer used, graduated 0-2600 rpm and with adjustable input frequency.
44 pulses/r (420/620 engines)
48 pulses/r (520/720 engines)
Diagnostic lamp
Max. power 3 W
Voltage 24 V

Diagnostic button
Switch type, closing (NO), spring biased.
To read the fault codes, please refer to the “Fault finding” chapter.
VODIA input
Deutsch 6-pin connector
To read the fault codes, please refer to the “Fault finding” chapter.

Parameter setting of Volvo Penta Engine

Adjustable parameters
The VODIA tool (including Penta EDC 4 software) can be used to read and adjust the parameters below, in “Parameter Programming” mode. For instructions, see “VODIA User´s Guide”.
NOTE! Special authorization is needed to be able to adjust certain parameters.
Coolant temperature protection (Special authorization needed)
Chooses whether engine protection should be activated in relation to high coolant temperature.
Alternative positions “Off” or “On”
Default value: “On”
If “On”, the coolant temperature warning lamp lights up at 110 °C (goes out at 109°C)
The engine is shut off at 113 °C after 30 sec.
Coolant level protection (Special authorization needed)
Chooses whether engine protection should be activated in relation to low coolant level.
Alternative positions “Off” or “On”
Default value: “On”
If “On”, the control unit does not check this function until 25 s after starting. When the control unit receives a low coolant level signal, the engine is shut off after 5 sec.
Oil pressure protection (Special authorization needed) Chooses whether engine protection should be activated in relation to low oil pressure.
Alternative positions “Off” or “On”
Default value: “On”
If “On”, the control unit does not check this function until 30 s after starting.
The limit values depend on engine speed. The oil pressure warning lamp lights up when the limit value is reached, and goes out again when the oil pressure has risen 10 % above the limit value. The engine is shut off when oil pressure falls to 80 % of the limit value. Examples of default values: 800 rpm – the oil pressure warning lamp lights up at 0.9 bar (goes out at 1 bar) and the engine is shut off at 0.72 bar.
2000 rpm – the oil pressure warning lamp lights up at 2.5 bar (goes out at 2.75 bar) and the engine is shut off at 2 bar.

Read-only parameters
The VODIA tool (including Penta EDC 4 software) can be used to read the values below in “Log test” mode.
For instructions, see “VODIA User´s Guide”.
• Battery voltage
• Coolant temperature
• Charge air pressure
• Oil pressure
• Fuel temperature
• Engine speed
• Throttle control %
• Droop %
• Throttle control voltage (Only in “Parameter, programming” position on VODIA tool)
• Engine total running time
• Engine load %

Fine adjustment, engine speed regulator

Use the VODIA tool (including Penta EDC 4 software), to read and adjust the P, I and D sections of the engine speed regulator. In some cases, this can offer more stable and more even engine running.
PID = Proportional, Integrating, Differential
The P section amplifies (Gain). A reduced value (Fig. 1) gives slower regulator reaction with change of load. An increased value (Fig. 2) gives a faster reaction. The I section stabilizes (Stability). A reduced value (Fig. 3) increases the time for system recovery with change of load. An increased value (Fig 4) gives a shorter recovery time.
The D section stabilizes (Differential). Reacts to the magnitude of the engine speed change. A reduced value (Fig 4) gives reduced sensitivity. An increased value (Fig. 5) gives increased sensitivity. Before any adjustments are made, the current values of the P, I and D sections of the PID regulator should be noted.
NOTE! Without the default values, the engine speed regulator/actuator can not be restored if adjustment is not successful.
For instructions, see “VODIA User´s Guide”.

Adjustment
1. Use the VODIA tool and note the current values of the P, I and D sections of the PID regulator.
2. Start the engine.
3. Run the engine at working speed without load, and first increase the value of the P section of the PID regulator until unstable (oscillating) engine speed is achieved. Then reduce the parameter by 1-2 % until the engine speed is stable again.
4. Then adjust the I section of the PID regulator in the same way as above.
5. If the engine still runs badly and no other adjustments help, increase the D section of the PID regulator until the engine only has a very small increase in speed when load is applied or removed, please refer to fig. 6.
NOTE! The few times that the D section may need to be adjusted include cases where the application has a flexible coupling or extremely low flywheel inertia.
6. Adjust the P and I sections again as above, if necessary.
7. Check the industrial generator engine response.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

How to Choose a Household Mini Generator

With the improvement of people's living standards, there are more and more household appliances, such as rice cookers, microwaves, kettles, refrigerators, air - conditioners, washing machines, etc. It can be said that every household has them. But what if there is a power outage? These appliances won't work properly, and our lives will be greatly disrupted. How can we avoid this? We can use household mini - generators to provide convenience in power consumption. So, how to choose a good household mini - generator? Consider the noise level Since it is for household use, when choosing a household mini - generator, we need to check whether the noise will affect the neighbors. Generally, the seller will demonstrate the performance of the generator in advance. A good household generator can reduce noise by about 80%. Choose a generator with a moderate price Due to different brands, there are significant differences in power, and consequently, the price differences of househ...

How to Choose Efficient Diesel Generators for the Film and Television Industry?

In the film and television industry, the stability of the electricity supply during filming is crucial. Whether the equipment are the cameras or the lighting equipment on the filming site, or the post-production equipment, they all need stable and reliable power support. Unstable or interrupted power can result in interrupted filming, damage to equipment, and even affecting the progress and quality of the entire project. Therefore, investing in high-efficiency diesel generator sets has become an important measure for the film and television industry to ensure the reliable power supply for shooting. Determine the power requirements Before choosing a diesel generator set for the film and television industry, it’s necessary to figure out the total power needs, including the electricity demand of the shooting location, the total power of the electrical equipment and the time of using electricity. Also consider whether there are special needs for the generators such as low noise level and...