Skip to main content

Connection and Parameter Setting of Volvo Industrial Engine


Connection of Volvo Industrial Engine

Control unit
The control unit must be installed separately from the engine. Control unit working temperature must be between - 40 °C to +85 °C.
Accelerator pedal (VE engines)
Idling: 0-5 V (standard value 0.3 V)
Full throttle: 0-5 V (default value 4.6 V)
A fault code is generated when the voltage is:
U > 4.9 V (standard value)
U < 0.1 V (standard value)
Engine speed potentiometer/external voltage input (GE engines)
Rotary potentiometer for fine adjustment of engine speed (GE engines)
On 1500 rpm or 1800 rpm GE engines, the Volvo engine speed can be finely adjusted ±5 %. A fault code is generated when the voltage is:
U > 4.8 V (standard value)
U < 0.2 V (standard value)
This accelerator pedal/potentiometer corresponds to the control unit standard value (0.5 V or 4.5 V respectively).
The end position resistor is used to detect electrical faults in the accelerator/potentiometer (end position resistors are built into many accelerators/potentiometers and do not need to be added in these cases).
1500/1800 rpm switch
This function makes it possible to switch engine speed between 1500 and 1800 rpm. Switch type, two-position (NO).
Droop switch
The switch must be closed to obtain droop. Switch type, two-position (NO).
Alarm, low oil pressure
Max. power 3 W
Voltage 12 V/24 V
Alarm, high coolant temperature
Max. power 3 W
Voltage 12 V/24 V

Tachometer
Tachometer used, graduated 0-2600 rpm and with adjustable input frequency.
44 pulses/r (420/620 engines)
48 pulses/r (520/720 engines)
Diagnostic lamp
Max. power 3 W
Voltage 24 V

Diagnostic button
Switch type, closing (NO), spring biased.
To read the fault codes, please refer to the “Fault finding” chapter.
VODIA input
Deutsch 6-pin connector
To read the fault codes, please refer to the “Fault finding” chapter.

Parameter setting of Volvo Penta Engine

Adjustable parameters
The VODIA tool (including Penta EDC 4 software) can be used to read and adjust the parameters below, in “Parameter Programming” mode. For instructions, see “VODIA User´s Guide”.
NOTE! Special authorization is needed to be able to adjust certain parameters.
Coolant temperature protection (Special authorization needed)
Chooses whether engine protection should be activated in relation to high coolant temperature.
Alternative positions “Off” or “On”
Default value: “On”
If “On”, the coolant temperature warning lamp lights up at 110 °C (goes out at 109°C)
The engine is shut off at 113 °C after 30 sec.
Coolant level protection (Special authorization needed)
Chooses whether engine protection should be activated in relation to low coolant level.
Alternative positions “Off” or “On”
Default value: “On”
If “On”, the control unit does not check this function until 25 s after starting. When the control unit receives a low coolant level signal, the engine is shut off after 5 sec.
Oil pressure protection (Special authorization needed) Chooses whether engine protection should be activated in relation to low oil pressure.
Alternative positions “Off” or “On”
Default value: “On”
If “On”, the control unit does not check this function until 30 s after starting.
The limit values depend on engine speed. The oil pressure warning lamp lights up when the limit value is reached, and goes out again when the oil pressure has risen 10 % above the limit value. The engine is shut off when oil pressure falls to 80 % of the limit value. Examples of default values: 800 rpm – the oil pressure warning lamp lights up at 0.9 bar (goes out at 1 bar) and the engine is shut off at 0.72 bar.
2000 rpm – the oil pressure warning lamp lights up at 2.5 bar (goes out at 2.75 bar) and the engine is shut off at 2 bar.

Read-only parameters
The VODIA tool (including Penta EDC 4 software) can be used to read the values below in “Log test” mode.
For instructions, see “VODIA User´s Guide”.
Battery voltage
Coolant temperature
Charge air pressure
Oil pressure
Fuel temperature
Engine speed
Throttle control %
Droop %
Throttle control voltage (Only in “Parameter, programming” position on VODIA tool)
Engine total running time
Engine load %

Fine adjustment, engine speed regulator

Use the VODIA tool (including Penta EDC 4 software), to read and adjust the P, I and D sections of the engine speed regulator. In some cases, this can offer more stable and more even engine running.
PID = Proportional, Integrating, Differential
The P section amplifies (Gain). A reduced value (Fig. 1) gives slower regulator reaction with change of load. An increased value (Fig. 2) gives a faster reaction. The I section stabilizes (Stability). A reduced value (Fig. 3) increases the time for system recovery with change of load. An increased value (Fig 4) gives a shorter recovery time.
The D section stabilizes (Differential). Reacts to the magnitude of the engine speed change. A reduced value (Fig 4) gives reduced sensitivity. An increased value (Fig. 5) gives increased sensitivity. Before any adjustments are made, the current values of the P, I and D sections of the PID regulator should be noted.
NOTE! Without the default values, the engine speed regulator/actuator can not be restored if adjustment is not successful.
For instructions, see “VODIA User´s Guide”.

Adjustment
1. Use the VODIA tool and note the current values of the P, I and D sections of the PID regulator.
2. Start the engine.
3. Run the engine at working speed without load, and first increase the value of the P section of the PID regulator until unstable (oscillating) engine speed is achieved. Then reduce the parameter by 1-2 % until the engine speed is stable again.
4. Then adjust the I section of the PID regulator in the same way as above.
5. If the engine still runs badly and no other adjustments help, increase the D section of the PID regulator until the engine only has a very small increase in speed when load is applied or removed, please refer to fig. 6.
NOTE! The few times that the D section may need to be adjusted include cases where the application has a flexible coupling or extremely low flywheel inertia.
6. Adjust the P and I sections again as above, if necessary.
7. Check the industrial generator engine response.

Comments

Popular posts from this blog

Diesel Generator Power Ratings: Standby vs Prime vs Continuous

Diesel generator sets are commonly used in a variety of sectors due to their dependable performance and high efficiency. They can be used for emergency power supply in the event of a power cut or used in places without connection to a power grid. When selecting a diesel generator for your home or business, you need to consider many factors, such as generator’s ratings. In this article, we’ll explain the three basic rating types - standby, prime, and continuous in diesel generators. ISO-8528-1:2018 defines basic generator set rating categories based on four operational categories: Emergency Standby Power (ESP), Prime Power (PRP), Continuous Power (COP) and Limited-Time Running Prime (LTP). Read on and learn the application of power ratings for engines used in generating sets. Standby Power Rating Standby Power(ESP) is used to supply emergency power when the external power supply is interrupted, such as power outages. Standby power rated generators can supply reliable electricity as t...

What Should You Pay Attention to in Routine Maintenance of Diesel Generator Sets

In modern society, the stability of power supply is directly related to the operation efficiency of enterprises and people's quality of life. Diesel generators have become an indispensable backup power supply or main power source in various industries due to their high efficiency, durability and reliability. However, to ensure the smooth operation and optimal performance of the generator sets, regular maintenance is essential. Here is what you need to pay attention to in the routine maintenance of diesel generators. Keep your generator clean It’s important to keep the generator’s exterior and the generator room clean. Regularly remove any dirt, dust, or debris that may accumulate to on the generator’s surface. This is not only for the sake of beauty, but also for the smooth operation of the unit. Cleaning the generator’s exterior, air intake vents, exhaust outlets and generator room can effectively reduce the risk of generator overheating. In addition, check if the connection bol...

How to Connect A Diesel Generator to Your House?

Diesel generators are fuel-efficient and reliable, which can almost meet the power needs of any application. If you want to power the whole house during power shortages, it’s a good choice to choose a diesel generator set as the backup electricity supply. But how to connect a diesel generator to your house? Read on and you will find the answer. Options to connect a diesel generator to your home   Keep in mind that never plug your generator directly into the mains, or it will cause back feeding, damage your appliances and be life-threatening for utility workers. Generally, you can choose to connect a generator to your house by using extension cords or a transfer switch. Understanding the difference between them is helpful for you to choose the right type. Extension cords   Typically, extension cords are suitable for smaller diesel generators that used for short term. They require no installation and are cost-effective. If you need to power only some basic appliances such as...