Connection of Volvo Industrial Engine
Control unit
The control unit must be
installed separately from the engine. Control unit working temperature must be
between - 40 °C to +85 °C.
Accelerator pedal (VE engines)
Idling: 0-5 V (standard value 0.3
V)
Full throttle: 0-5 V (default
value 4.6 V)
A fault code is generated when
the voltage is:
U > 4.9 V (standard value)
U < 0.1 V (standard value)
Engine speed
potentiometer/external voltage input (GE engines)
Rotary potentiometer for fine
adjustment of engine speed (GE engines)
On 1500 rpm or 1800 rpm GE
engines, the Volvo engine speed can be finely adjusted ±5 %. A fault code is
generated when the voltage is:
U > 4.8 V (standard value)
U < 0.2 V (standard value)
This accelerator
pedal/potentiometer corresponds to the control unit standard value (0.5 V or
4.5 V respectively).
The end position resistor is used
to detect electrical faults in the accelerator/potentiometer (end position
resistors are built into many accelerators/potentiometers and do not need to be
added in these cases).
1500/1800 rpm switch
This function makes it possible
to switch engine speed between 1500 and 1800 rpm. Switch type, two-position
(NO).
Droop switch
The switch must be closed to
obtain droop. Switch type, two-position (NO).
Alarm, low oil pressure
Max. power 3 W
Voltage 12 V/24 V
Alarm, high coolant temperature
Max. power 3 W
Voltage 12 V/24 V
Tachometer
Tachometer used, graduated 0-2600
rpm and with adjustable input frequency.
44 pulses/r (420/620 engines)
48 pulses/r (520/720 engines)
Diagnostic lamp
Max. power 3 W
Voltage 24 V
Diagnostic
button
Switch type, closing (NO), spring
biased.
To read the fault codes, please
refer to the “Fault finding” chapter.
VODIA input
Deutsch 6-pin connector
To read the fault codes, please
refer to the “Fault finding” chapter.
Parameter
setting of Volvo Penta Engine
Adjustable
parameters
The VODIA tool (including Penta
EDC 4 software) can be used to read and adjust the parameters below, in
“Parameter Programming” mode. For instructions, see “VODIA User´s Guide”.
NOTE! Special authorization is
needed to be able to adjust certain parameters.
Coolant temperature protection
(Special authorization needed)
Chooses whether engine protection
should be activated in relation to high coolant temperature.
Alternative positions “Off” or
“On”
Default value: “On”
If “On”, the coolant temperature
warning lamp lights up at 110 °C (goes out at 109°C)
The engine is shut off at 113 °C
after 30 sec.
Coolant level protection (Special
authorization needed)
Chooses whether engine protection
should be activated in relation to low coolant level.
Alternative positions “Off” or
“On”
Default value: “On”
If “On”, the control unit does
not check this function until 25 s after starting. When the control unit
receives a low coolant level signal, the engine is shut off after 5 sec.
Oil pressure protection (Special
authorization needed) Chooses whether engine protection should be activated in
relation to low oil pressure.
Alternative positions “Off” or
“On”
Default value: “On”
If “On”, the control unit does
not check this function until 30 s after starting.
The limit values depend on engine
speed. The oil pressure warning lamp lights up when the limit value is reached,
and goes out again when the oil pressure has risen 10 % above the limit value.
The engine is shut off when oil pressure falls to 80 % of the limit value.
Examples of default values: 800 rpm – the oil pressure warning lamp lights up
at 0.9 bar (goes out at 1 bar) and the engine is shut off at 0.72 bar.
2000 rpm – the oil pressure
warning lamp lights up at 2.5 bar (goes out at 2.75 bar) and the engine is shut
off at 2 bar.
Read-only
parameters
The VODIA tool (including Penta
EDC 4 software) can be used to read the values below in “Log test” mode.
For instructions, see “VODIA
User´s Guide”.
• Battery
voltage
• Coolant
temperature
• Charge air
pressure
• Oil
pressure
• Fuel
temperature
• Engine
speed
• Throttle
control %
• Droop %
• Throttle
control voltage (Only in “Parameter, programming” position on VODIA tool)
• Engine
total running time
• Engine load
%
Fine
adjustment, engine speed regulator
Use the VODIA tool (including
Penta EDC 4 software), to read and adjust the P, I and D sections of the engine
speed regulator. In some cases, this can offer more stable and more even engine
running.
PID = Proportional, Integrating,
Differential
The P section amplifies (Gain). A
reduced value (Fig. 1) gives slower regulator reaction with change of load. An
increased value (Fig. 2) gives a faster reaction. The I section stabilizes
(Stability). A reduced value (Fig. 3) increases the time for system recovery
with change of load. An increased value (Fig 4) gives a shorter recovery time.
The D section stabilizes
(Differential). Reacts to the magnitude of the engine speed change. A reduced
value (Fig 4) gives reduced sensitivity. An increased value (Fig. 5) gives
increased sensitivity. Before any adjustments are made, the current values of
the P, I and D sections of the PID regulator should be noted.
NOTE! Without the default values,
the engine speed regulator/actuator can not be restored if adjustment is not
successful.
For instructions, see “VODIA
User´s Guide”.
Adjustment
1. Use the VODIA tool and note
the current values of the P, I and D sections of the PID regulator.
2. Start the engine.
3. Run the engine at working
speed without load, and first increase the value of the P section of the PID
regulator until unstable (oscillating) engine speed is achieved. Then reduce
the parameter by 1-2 % until the engine speed is stable again.
4. Then adjust the I section of
the PID regulator in the same way as above.
5. If the engine still runs badly
and no other adjustments help, increase the D section of the PID regulator
until the engine only has a very small increase in speed when load is applied
or removed, please refer to fig. 6.
NOTE! The few times that the D
section may need to be adjusted include cases where the application has a
flexible coupling or extremely low flywheel inertia.
6. Adjust the P and I sections
again as above, if necessary.
7. Check the industrial generator engine response.
Comments
Post a Comment