This article mainly introduce how to start and stop diesel generator set with right steps.
Notice:
*Press the
emergency button or switch the control switch to “STOP” to stop the engine at
any time.
*Before
restart, release the emergency stop button and rotate clockwise. Meanwhile,
switch the control switch manually to “STOP”.
1. Examine
before start the machine according to Chapter 5.2
2. Connect
battery to the engine, first positive electrode and then load.
3. Check
whether the engine oil is filled to the assigned level.
4. Check
whether water is filled.
5. Discharge
the air in fuel system.
Connect and start the abnormal
fueling system will cause unburned oil accumulated in the smoke evacuation
system, bringing potential explosion risk.
4.Fill the
fuel supply system with manual fuel tank and discharge the air accumulated in
the oil filter. (For more detail information, please refer to the “Diesel
Manual”)
Start:Put the main controller to start position
manually and press the start button. The diesel will automatically start for
three times until started. If failed to start, the control system will lock at
“starting failure” while the fault indicator on the control panel will be on.
Under this condition, please refer to the “Diesel Manual” to find out the
reason of starting failure.
If failed to start for many
times, dismount the connector of the smoke evacuation pipe to disperse the
unburned oil gas. Once the oil gas (white smog) dispersed and other faults for
starting failure are rejected, reinstall the exhaust pipe and restart.
6.Check whether there’s unusual noise or
vibration.
7.Check the cooling liquid and smoke evacuation
system for leakage.
8. Check the control panel indicator lights for
abnormality, especially for unusual high temperature or extremely low oil
pressure. The oil pressure shall be in normal range 10s after the starting.
9.Check the voltage and frequency displayed on
control panel. Voltage is the indicating rated voltage set by the factory and
the load frequency of generating set with 50 cyclic waves is about 52 cyclic
waves and 62 cyclic waves for generating set with 60 cyclic waves. (Electronic
governor or cyclic wave of EFI unit can be pre-set an ideal value close to the
rated cyclic wave.) There are three ways for voltage adjustment: if the control
panel installed with voltage adjustment potentiometer, voltage can be adjusted
through it; fine adjustment can be achieved through a potentiometer installed
in the automatic voltage adjuster in the terminal box of alternator; output
voltage alternation requires to change the coil of alternator with the coil
joint stored in the terminal box.
For more
information on connection, please refer to the “Alternator Manual”.
Cutoff switch is not allowed to
switch on during the phase examination.
10.When the electric generator already produced
voltage, install the phase meter on one side of the cut off switch of the
generator for phase examination, which shall be implemented by qualified
technicians.
11.Stop machine:If press the emergency stop button, the machine
will stop running immediately. If press the manual stop button, the machine
will stop according to the set procedures.
12.Check the remote control device, release the
emergency stop button and put the controller on “AUTO” Input the remote control
signal and the engine will start according to the above mentioned procedures.
Clear the remote control signal and the engine will stop immediately.
Notice:When receive stop order, control system will
control the engine to run continuously for a while depending on the cooling
time before the automatic stop for the purpose of cooling.
13.Now the load cable can be connected and the
generator is ready for normal operation.
5.4 Normal
manual start / stop------Automatic start control panel (normal start and stop)
Notice:
* Press the
emergency stop button and the generator will stop at any time.
* The
emergency stop button shall be reset by clockwise rotation before restart.
1. Examine before start according to the
description in Chapter 5.2.
Notice:
* It is not
allowed to start the machine when the fault indicator light is on. Turn
off the
controller again and reconnect to the power switch for entering into a start
procedure. Make sure all faults cleared before start.
2.Manual start: Make sure the emergency stop
button reset. Put the manual button of controller to manual position and press
the start button, releasing it when the indicator light above the start button
is on. At this moment, controller enters into starting procedure and diesel
will automatic start for 3 times until started. If the diesel failed to start,
controller will display “starting failure” and fault indicator light on the
control panel will be on. Under this condition, please refer to the 9th section
to find out the fault or refer to refer to the “Diesel Manual” to find out the
reason of starting failure.
The unburned
oil gas accumulated in the smoke evacuation pipe caused by many times starting failures
is of explosive danger. Therefore, first disconnect the joint or pipe of the
exhaust pipeline to let the white oil smog disperse, and find out the starting
failure faults, and then reinstall the exhaust pipeline for restart.