Inspection and Operation of Starlight AC Generator



a. Though the generator, AVR and auxiliary devices are solid and well insulated, if the generator was stored for longtime it might be moistened, and should be inspected carefully before operation.
b. Measure the insulating resistance, of winding against the ground by ohmmeter, if the value is less than 2 in cold condition, the generator should be dried. Caution: At measuring, the electronic elements and capacitor should be shorted, and the AVR. should be disconnected to avoid damaged.
c. Make sure all connecting joints are tight and contact good.
d. Be sure the frame is properly grounded, and ground wire should be same as the size of lead-wires
e. Make familiar with the rated data of nameplate before operation.

2. Voltage adjustment
In general, the generator was carefully inspected and tested in operation before it left the factory, and the normal voltage has been corrected, so it is not necessary to adjust. If necessary, the setting potentiometer of voltage may be adjusted again. If the external potentiometer is used for remote control , it also can be adjusted to set the voltage.

3. AVR. Wiring
The wiring diagram of Sx440 and APR125-5 are shown as Fig .1 Fig .2. The end 3 and 4 of AVR are also connected to the 190V-240V, but there is a plug wire that should be put in the "50Hz" or "60Hz" position.


Operation

After inspection and adjustment have been made, and no trouble is found , the generator can run normally and generate the electricity. In order to keep generator run well, please remember following notices;

a. The generator output must be disconnected from the load , then start the prime mover.

b. Check the speed and adjust to the rated RPM, the voltage of generator w… get to normal value, then close the main circuit breaker to the load. The genset speed may be changed under load , and frequency may be tower than the normal frequency , check and adjust the speed as necessary.

c. Before shut down the genset, remove load and turn off the main circuit breaker. This is especially important, or the loss of residue magnetism can result.

d. If starting up the generator for first time or the generator stored for longtime, generator may be loss of the residue magnetism, and voltage can not built up,should charge to F+ and F- with DC 12V voltage , the "+" touch to F, and the" -" touch to F- for 15-20 seconds. Caution: the generator must be stud still during charging the magnetism, or AVR may be damaged.

e. Three phase AC generator should be operated at balanced load. Should pay more attention to the load and the balance of current to prevent the generator loaded on the single phase or serious unbalancing condition, or the AVR. and generator can be damaged.

The following image shows Starlight generator manufacturing workshop.




Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...