MX generators are suitable for
paralleling as full damping winding. But, before paralleling, each unit of
generator should be started up, operated and adjusted.
A. Base conditions of paralleling
operations:
1 . Additional paralleling
circuitry
a. Voltage regulator-paralleling
provisions
b. Paralleling current
transformer(s)
c. Paralleling provisions on
governor controls
d. Switch gear
2. The voltage and frequency must
be the same for all sets with voltages in phase.
3. The generators must have the
same phase sequence rotation.
4. The voltage regulation
characteristics of the individual generators should be similar.
5. The driving engines should
have the same speed regulation characteristics and the governors should be
adjusted to give the same speed regulation.
B: Reactive load control and
adjustment:
When two identical generators are
operating together in parallel and an unbalance occurs in field excitation,
circulating currents begin to flow between the generators. This current will appear
as a lagging power factor or inductive load to the highly excited generator,
and as a leading power factor or capacitive load to the generator with the
lower field current. This is known as the reactive circulating current, and
there are two controlling methods in parallel operation:
1. Reactive droop compensation
(formerly known as parallel droop compensation) - the bus voltage droops or
decreases as the reactive lagging power factor load is increased. Then the
output current and power of generator decreases, thus reactive power tends to
balance.
2. Reactive differential
compensation (formerly known as cross current compensation) - the reactive
differential compensation circuit allows parallel generators to share reactive
loads with no decrease or no droop in generator voltage, The circuit must meet
the following criteria:
a. All secondary circuit of
current transformers for generators being paralleled must be included into
interconnection loop.
b. When different size generators
are paralleled, all paralleling current transformers must have the same or
proportional ratios that give approximately the same secondary current.
c. Reactive differential
compensation cannot be used when paralleling with the utility power. There is
no limit, however, in the number of generators that can be included in this
type of circuit.
The paralleling with the utility
power has different wiring circuitry, means and program, consult with
manufacturer if need assistance.
VIII. Thyristor or SCR Loading
Solid state electronic control
devices which utilize thyristors or SCR firing circuits (such as variable
frequency induction motor controls, precision motor speed controls, no-break
powered battery chargers, etc.) can introduce high frequency harmonics which
adversely affect or destroy the normal waveform of the generator. This creates
additional heat in the generator stator and rotor and can cause overheating.
These devices can and do present
problems to non-utility power generating equipment or any limited power bus
system. The problems which can occur are not limited to the generator itself,
but can effect the solid state control device, the equipment it controls, other
associated loads, monitoring devices, or a number of combinations over the
entire system.
MAGNAMAXDVR generators can supply
power to thyristor or SCR loads when properly applied. When SCR loads are more
than 25% of the total load, select the generator based on the 800C R/R rating.
The standard voltage regulator is PMG powered and senses 3 phase RMS voltages
for maximum stability against severely distorted wave forms. SCR type
applications such as cranes, shovels, etc., require special consideration of
the generator insulation system due to greater dielectric stress and severe
environmental conditions. Please contact to Marathon Electric for application
assistance.
Ⅸ.Troubleshooting
Symptom: Generator Produces No Voltage or Residual Voltage
|
|
Regulator Fuse
Blown
|
Check fuses with
an ohmmeter. Replace bad fuse, Refer to regulator manual.
|
Voltmeter Off
|
Check to be sure
meter phase selector switch is not in the off position.
|
Incorrect
Connections
|
Verify generator
connections (refer to drawings supplied with generator set or principle
diagram).
|
Defective
Connections/Wiring
|
Inspect all wiring
for grounds, open circuits, and short circuits.
|
Defective
Voltmeter
|
Verify proper operation
of panel meter with another meter that is known to be accurate.
|
No Regulatar
Input
|
Measure voltage
at regulator input (PMG output).
|
Defective Diodes,
Surge Suppressor Generator Windings
|
Test generator
with constant excitation (12 volt or battery test).
|
Voltage Regulator
Protective Shutdown Circuits are Operating
|
Correct problem
and adjust regulator. Refer to regulator manual.
|
Voltage Regulator
Inoperative
|
Adjust or replace
regulator. Refer to regulator manual.
|
Symptom: Generator Produces Low Voltage - No Load
|
|
Under speed
operation
|
Check speed using
tachometers and/or frequency meters.
|
Defective
Voltmeter
|
Disconnect F1 and
F2 leads at the voltage regulator. If voltage goes down, continue to
next step. If voltage does not change, refer to Troubleshooting for
symptoms of “No Voltage – Residual Voltage”.
|
Incorrect
Generator Connections
|
Verify generator
connections (refer to drawings supplied with generator set).
|
Defective
Connections/Wiring
|
Inspect all
wiring for grounds, open circuits, short circuits, loose connections,
and dirty connections.
|
Regulator
Adjustments
|
Adjust regulator
(refer to regulator manual). Check exciter field volts.
|
Defective Diodes,
Surge Suppressor, Generator Windings
|
Test generator
with constant excitation (12 volt or battery test).
|
Symptom: Generator Produces Low Voltage When Load Is Applied
|
|
Overload
|
Measure amps and
verify that the load does not exceed the nameplate rating of the
generator.
|
Overload -
Defective Ammeter
|
Verify
operation of ammeter by using a separate meter that is known to
be accurate.
|
Droop Circuit
|
If the generator
set is equipped for paralleling, some voltage droop is normal as load
increases (refer to the regulator instruction manual).
|
Line drop
|
The sensing point
far away from the measuring point of voltage meter, it may has some
voltage drop on the longer line.
|
Symptom: Generator Produces High Voltage
|
|
Defective
Voltmeter
|
Verify operation
of panel meter with another meter that is known to be accurate.
|
Incorrect
Operating Speed
|
Verify speed with
tachometer or frequency meter.
|
Incorrect
Connections
|
Verify generator
connections.
|
Defective
Connections/Wiring
|
Inspect all
wiring for grounds, open circuits, and short circuits.
|
Regulator
Adjustments
|
Adjust regulator
(refer to regulator manual).
|
Diode Polarity
Incorrect
|
Check diodes:
verify proper diodes are installed and polarity is correct.
|
Voltage Regulator
Not Operating Properly
|
Adjust or replace
regulator (refer to regulator instruction manual).
|
Symptom: Generator Voltage Is Fluctuating
|
|
Incorrect Speed
|
Verify speed with
tachometer or frequency meter.
|
Unstable Speed
|
Verify governor
stability.
|
Voltage Regulator
Stability
|
Adjust regulator
stability (refer to regulator manual).
|
Defective/Loose
Connections
|
Inspect all
wiring for loose or dirty connections.
|
Test generator
with constant excitation (12 volt battery test).
|
|
Remote Voltage
Adjust (If used)
|
Check operation
(refer to regulator manual).
|
Defective
Regulator
|
Replace regulator
(refer to regulator manual).
|
SCR load
|
Check the load
situation, does it match.
|
Comments
Post a Comment