Diesel Genset Noise Source And Useful Solutions

The noise of generator set is mainly comes from engine and generator. To reduce the noise of the generator set, it is necessary to control the noise source. This article will show you the detailed information about the genset noise source as well as the solution.

The main noise source of engine is as follows:

Induction noise
Exhaust noise
Combustion noise
Mechanical noise
Cooling fans noise

The main noise source of generator is as follows:

Ventilation noise
Electromagnetic noise
Mechanical noise

Main noise source of engine

1. Air intake and exhaust system noise is the most powerful noise source of the engine.

The main source of intake noise is as follows:

1) The pressure fluctuation of air in the intake pipe, which results in low frequency noise.
2) The air flows through the flow area of the intake valve at high speed, which results in high frequency eddy noise.
3) The noise of turbocharger compressor
4) The noise of scavenging pump for two-stroke diesel engine

The main source of exhaust noise is as follows:

1) The pressure fluctuation of exhaust gas in the exhaust pipe, which results in low and intermediate frequency noise.
2) High frequency eddy current noise at the flow area of exhaust valve.

2. Combustion noise

Combustion noise is the main noise source of internal combustion engine. The burning of combustible mixture in the cylinder causes a sharp change of gas pressure. The piston, cylinder liner, connecting rod, piston pin and crankshaft parts are subjected to impact load, which causes structural vibration and noise.

3. Mechanical noise

The main components to cause mechanical noise include piston, cylinder head, cylinder liner, cylinder block, connecting rod, piston pin, crankshaft, valve gear, drive gear and fuel injection pump, etc. Therefore, the design of these parts, manufacturing quality as well as the material selection have an important effect on the noise. The diesel engine stiffness, rotating speed, and movement clearance are the main factors to afftect the mechanical noise.

4. Cooling fan noise

It results from the sound of air being moved at high speed across the engine and through the radiator.

Main noise source of generator

1. Ventilation noise

It includes fan and other ventilation equipment as well as the gas weirl noise formed by rotor. Fan rotation makes cooling gas periodic fluctuation so as to produce the single frequency noise. Resonance of thin wall parts in wind path, or the “piping” produced due to unreasonable return circuit design.

2. Electromagnetic noise

The noise refers that due to the interaction of stator and rotor magnetic field in generator air gap, it produces radial force changing with time and space, causing stator core and engine base to vibration due to periodic deformation over time so as to produce noise.

3. Mechanical noise

The mechanical noise of generator includes the mechanical vibration noise (caused by centrifugal force that is produced by rotor mechanical unbalance), bearing ventilation noise, brush connector ring or commutator sliding contact noise, and the axial vibration noise of end cap excited by bearing vibration.

Noise Reduction Measures

There is no doubt that it will have certain effects on the surrounding environment and personnel if the working noise of the machine is too large. Therefore, some necessary noise reduction measures should be taken. In addition to reduce the noise of generator set itself, it is also important to carry out special design for generator room.

1. Room sound insulation

The room door and window should adopt fireproof sound insulation door and window. Besides, the sound insulation requirement of brick wall needs more than 40dB (a). On the other hand, it is also important to eliminate sound paths through cracks in doors or walls.

2. Air intake and exhaust

After dealing with room sound insulation,  you should turn to solve the problem of ventilation and heat dissipation in the generator room. The air inlet shall be in the same line as the generator set and the air outlet. The air inlet shall be equipped with resistive chip muffler. Due to the air inlet pressure loss is within the allowable range, it can make the air flow in the room reach balance naturally, meanwhile, the effect of ventilation and heat dissipation is obvious.

3. Exhaust muffler

In general, generator set is always equipped with an exhaust muffler to limit exhaust noise from the machine. Exhaust silencer comes in a wide variety of types, it is usually divided into two types: chamber-type silencer and spiral type device. The chamber-type device tends to be more effective, but the spiral-type device is more compact and may provide sufficient attenuation for many equipments.

4. Sound absorption treatment

In the machine room, the five walls except for the ground can be used for sound absorption treatment. According to the frequency spectral characteristic of the generator set, the perforation board resonance sound absorption structure is adopted. In addition, acoustic insulation – sound-absorbing materials are available for lining air ducts and covering walls and ceilings. Reducing noise at a wall covered in sound absorbing material can be very effective.

5. Air exchange in the room

Good sound insulation in the generator room will make there is no air convection in the machine room when the closed water-cooled generator set power off, the high temperature in the room can’t be lowered in time. To solve the problem, you can adopt low noise axial flow fan and equip with a resistive chip muffler.

6. Cooling air attenuation

Inlet and outlet air attenuation baffles can help reduce the noise produced by the cooling air as it moves across the engine and through the radiator.

7. Unit vibration isolation

Before installing the generator set, users should strictly follow the relevant information provided by the manufacturer to carry out vibration isolation treatment so as to avoid the long-distance transmission of structural sound, which continuously radiate air noise in the propagation so that the factory noise level fail to reach standard. For the generator units that are required to deal with due to exceed standard, the vibration of the ground near the unit must be measured. If the vibration is obvious, the vibration isolation treatment of the generator set must be carried out first.


Comments

Popular posts from this blog

What Is the Difference Between Electric Motor and Electric Generator

An electric motor is an electrical machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and winding currents to generate force. In certain applications, such as in regenerative braking with traction motors, electric motors can be used in reverse as generators to recover energy that might otherwise be lost as heat and friction. An electric generator operates in the reverse direction, converting mechanical energy into electrical energy. Electric generator can be divided into various type, open type, silent type, trailer type, portable type and container type, etc. Electric generator is mainly composed of diesel engine & alternator. Electric generator set is mainly composed of engine, alternator, control module, and common base. Electric generator :- Electric generator is a type of machine which converts mechanical input (energy) into electrical output (...

Engine Fault Code Messages - Volvo Penta Engine

Volvo Penta Engine Fault Code When a malfunction has occurred and the diagnostic system has generated one or more fault codes, these are read out differently depending on the equipment used. Please refer to “Fault code messages”. If the system indicates that a fault code has been set: 1 Cut engine speed to idle, or shut the Volvo engine off. 2 For DCU/DU Read the fault code from the display, please refer to Reading fault codes via the DCU or Reading fault codes via the DU. For CIU press the diagnostic button and read the fault code, by observing the flashing of the diagnostic lamp. Refer to Reading fault codes via the diagnostic lamp, CIU. 3 Look up the fault code in the Fault Code Register chapter and take the recommended measures. Reading fault codes via the DU (Display Unit) Depending on the severity of the fault the text, either WARNING! or ALARM STOP (a buzzer sounds) will be shown on the display 1 Press any button to come to the fault list. The f...

Yuchai 4D24 & 4D24T Series Diesel Engine Operation Guide

Yuchai 4D24 & 4D24T series off-highway diesel engines are developed by RAYWIN POWERTRAIN TECHNOLOGY CO., LTD. with international engine R&D institutions together. Adopted tunnel block, rotary fuel pump (mechanic or electric governor), turbocharged/naturally aspirated and 2-valve technologies, 4D24 series engines are with reliable, fuel-efficient and strong power characters. It could be applied for agriculture & garden fields, construction equipment, power generation , marine and industrial equipment. General Safety Rules Incorrect procedures, carelessness or neglect of warning instructions may cause burns, cuts, body mutilation, asphyxiation or other injury or even death. Before maintenance, please read and understand all the security measures instructions and warnings carefully. The following pages contain a general security measures to ensure personal safety that you should follow. ◆ Maintenance area should be dry, bright and well ventilation, no sund...