Generator is a device that converts mechanical energy
into electrical energy for use in an external circuit. At present, generators
are widely used in industry and agriculture, national defense, science and
technology as well as our daily life.
Working
principle of generator
Generator works by moving electrical conductors through a
magnetic field. If your generator doesn’t have magnets, it won’t produce
electricity. The magnetic field is created by taking some of the generator
output voltage and converting it to DC and feeding it to a coil to make an
electro magnet.
Nowadays, the generator degree of automation is high, the
control circuit is also complex, thus, some faults may occur when the generator
set is at work, which directly affect the normal power supply operation of the
unit. So during the normal
operation of the genset, except monitoring and analyzing the data on system
instrument, it is also necessary to observe whether the parameters of the
generator on each instrument are within the normal range or not.
Why a
generator won’t produce electricity? This
is a hot topic that many users care about. Next, I will analyse the reasons for
you.
1. The residual
magnetism of the generator core
is disappeared or too weak.
The residual magnetism can be lost naturally when the
genset is placed too long or it can also happen from running a generator with
no load for too long. However, for the new genset, the residual magnetism can
be lost due to a long distance transportation vibration. Thus, it will cause
the remanence voltage of generator is disappeared or less than normal remanence
voltage value, namely, the remanence line voltage is less than 10V, the
remanence phase voltage is less than 6V. Because
the stator of synchronous generator, rotor, as well as AC exciter stator, and
rotor core are usually folded by adopting 1~1.5mm thick silicon steel sheet.
After excitation vibration, the residual magnetism is easy to disappear or
weaken. When the residual magnetism is lost, the generator will produce no
power at start-up.
2. Excitation circuit wiring error
The polarity of the excitation winding is reversed. After electrifying, the magnetic field
produced by the field winding current is counteracted with the residual
magnetism, resulting in the disappearance of the remanence. In addition,
when measuring the DC resistance of the excitation winding or testing the
automatic voltage regulator AVR, without paying attention to the polarity,
which will also cause the core remanence to disappear.
3. Excitation circuit is blocked
In the generator excitation circuit, the electrical
contact is bad or the wiring head of each electrical component is loose, the
lead wire is broken, causing the circuit to be interrupted, and the generator
excitation winding has no excitation current.
4. Circuit for DC side of rotary rectifier is interrupted
Due to the interruption of circuit for DC side of rotary
rectifier, therefore, after the AC exciter is rectified by the rotary
rectifier, the excitation current supplied to the excitation winding can not be
sent into the excitation winding, resulting in AC synchronous generator can not
generate electricity.
5. AC exciter fault, no output voltage
The generator can’t produce electricity due to AC exciter
failure, so that the excitation winding of the AC synchronous generator has no
excitation current.
6. Generator excitation winding is broken or grounded,
resulting in the generator has no excitation current or the excitation current
is minimal.
Solution
1. When the residual magnetism of the generator core
disappears, magnetizing treatment shall be carried out.
The magnetizing method:For the self-excited generator, usually using extra
battery or dry battery, using its positive and negative poles to supply
electricity for a short time towards the leading-out terminal of the excitation
winding. However, be sure to recognize the polarity of DC power supply and
excitation winding clearly, namely, the positive pole of the DC power supply is
connected to the positive pole of the excitation winding, and the negative pole
of the DC power supply is connected to the negative pole of the excitation
winding. If the control panel of diesel generator set is equipped with
magnetizing circuit, the toggle switch should be turned to “magnetizing”
position, which can magnetize the AC exciter.
2. Excitation circuit wiring error, correct it after
searching.
3. Use multi-meter ohm block to find the excitation
winding broken line and connect it. For the failure caused by poor contact,
polish the surface oxide layer with find sand cloth, the loose connection bolt
and nut shall be firm.
4. Ground and broken line fault of excitation winding.
Use 500V ohmmeter to check the ground insulation of the excitation winding,
find out the ground point, use multi-meter to find out the broken line and
restore it.
Hope the above methods can help your restore your
generator output power. If it still fails. you need to replace the automatic
voltage regulator as it may be damaged.